3-5-2. Systems where electric energy is entered manually (no-metering-device method)

In systems where electric energy is entered manually (no-metering-device method), the charge rates will only be
printed out for each energy management block.
[1] Example of printed results for each energy management block
(Display order of charge calculation result: Number; Merger of energy management blocks with same name: Merge)
* In systems where electric energy is entered manually (no-metering-device method), the charge rates [%] will be output,
not the electric energy.
The respective total percentage of [Charge rate[%] (for indoor unit)] and [Charge rate[%] (for outdoor unit)] will be 100%. (If
there are multiple connected AE-200 units, the total for all the AE-200 units will be 100%.)
* If the electric energy is metered individually for indoor units and outdoor units, calculate the charges using the electric
energy for outdoor units and [Charge rate[%] (for outdoor unit)], and the electric energy for indoor units and [Charge
rate[%] (for indoor unit)].
If the electric energy is metered for indoor units or for indoor and outdoor units, calculate the charges using the electric
energy and [Charge rate[%] (for outdoor unit)].
* Of the data shown, those that should be used are [Charge rate[%] (for indoor unit)] and [Charge rate[%] (for
outdoor unit)]. The data in Apportionment Parameter (inclusive sum), Apportionment Parameter (for indoor unit) and
Apportionment Parameter (for outdoor unit) will not be used. (These values are for reference only.)