12.2. Self-check function, Function Table
• Refer to the installation manual that comes with each remote controller for details.
• RF thermostat is not established.
[Output pattern A] Errors detected by indoor unit
IR wireless remote controller
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes
(Number of times)
1
P1
2
P2, P9
3
E6, E7
4
P4
5
P5
6
P6
7
EE
8
P8
9
E4
10
–
11
PB
12
Fb
No sound
––
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
IR wireless re-
Wired remote
mote controller
controller
RF thermostat
Beeper sounds/
Check code
OPERATION
INDICATOR lamp
flashes
(Number of
times)
1
E9
2
UP
3
U3, U4
4
UF
5
U2
6
U1, Ud
7
U5
8
U8
Specifications are subject to change without notice.
NTXAMT12, 18, 24, 30, 36A112AA
RF thermostat
Check code
Intake sensor error
Pipe (Liquid or 2-phase pipe) sensor error
Indoor/outdoor unit communication error
Drain sensor error
Drain pump error
Freezing/Overheating safeguard operation
Communication error between indoor and outdoor units
Pipe temperature error
Remote controller signal receiving error
–
Fan motor error
Indoor unit control system error (memory error, etc.)
No corresponding
Symptom
Indoor/outdoor unit communication error (Transmitting
error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor
locked)
Abnormal high discharging temperature/49˚ C worked/
insufficient refrigerant
Abnormal high pressure (63H worked)/ Overheating safe-
guard operation
Abnormal temperature of heat sink
Outdoor unit fan protection stop
41
Symptom
Remark
For details, check the LED display of the outdoor controller
© 2022 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Remark
board.