6-7-2. Outdoor unit settings

Set the standby electric power for connected outdoor units.
Procedures
1. Click [Billing Function Settings] > [Outdoor Unit] to access the outdoor unit settings screen.
Target centralized
controller
Select one of the connected
centralized controllers
whose outdoor unit settings
are to be made.
Outdoor unit/sub outdoor
unit
Displays the outdoor units
and sub outdoor units set
in the refrigerant system
settings.
2. Check that the addresses of the outdoor units connected to the controller selected in "Target centralized
controller" are displayed in the "Outdoor unit/Sub outdoor unit" column.
Note
• The outdoor units and sub outdoor units set in section 6-6-2 "Refrigerant System settings" will be
displayed.
• (
) indicates an outdoor unit, and (
3. Enter "Standby electric power" in [kW].
Note
• Set the standby electric power for an outdoor unit between 0 and 1.000 [kW].
• The default setting of 0.070 [kW] is recommended.
• Where an outdoor unit (single address) is a model equipped with 2 compressors, it is recommended that
the standby electric power is set to twice the default setting (0.140 [kW]).
4. After the settings are completed, click [Save].
WT07442X02
Save
Click to save the settings.
) indicates a sub outdoor unit.
87
Standby electric power
Sets the standby electric
power for the outdoor unit.
Back
Click to display the previous
settings without making any
changes.