4. Clear the comparison data of AE-50/EW-50.
Comparison data
This is the data used to compare the latest values on the AE-50/EW-50 and PI controller with the values on
the AE-200 when the previous apportionment was calculated, and calculate the increment.
Clear the comparison data on the replaced AE-50 or EW-50 connected to the AE-200.
Select [Centralized controller] as the "Target".
Select the replaced AE-50 or EW-50 as the "Centralized controller" and then touch [Clear].
(With each touch, the display changes in the following sequence: [Exp1]→[Exp2]→[Exp3]→[Exp4].)
5. Clear the comparison data of PI controller.
If a PI controller is connected to the replaced AE-50 or EW-50 connected to the AE-200, carry out the
procedure below.
Touch [Maintenance] > [Apportioned data] > [Comparison data] and select [PI Controller] as the "Target".
Select the AE-50 or EW-50 where the PI controller is connected to as the "Centralized controller".
(With each touch, the display changes in the following sequence: [Exp1]→[Exp2]→[Exp3]→[Exp4].)
Select the address of the connected PI controller as the "PI Controller".
After the settings are completed, touch [Clear].
• Also carry out this procedure if using an AE-50 or EW-50 built-in Pulse Input (PI).
For built-in Pulse Input (PI), select [PI].
• This procedure is not required for an AE-50 or EW-50 with PI controller not connected.