(3) If there is a unit with "0" amount of operating electric energy
Check this using the AE-200 charge parameters (CSV file).
Procedures
1. Connect a USB memory to the AE-200.
2. Open the [Maintenance] > [CSV output] screen and, with [Charge Parameters] selected, touch [Output as
CSV file].
3. Open the CSV data.
Charge Parameters
4. Check the numeric value for the mode selected in "Outdoor unit electric energy consumption" mode in [Billing
Function Settings] > [Billing Function] on the Initial Setting Tool.
5. If the number is not "0", the setting may be incorrect.
If the number is "0", do the trial run of the air conditioning unit (cooling or heating) and check that the amount
of power usage has increased. If the amount does not increase, the setting may be incorrect.
* Refer to the AE-200 Instruction Book –Detailed operations– for detailed information on the charge parameters.
(4) If there is a unit with "0" amount of standby electric energy
Procedures
1. Check the system's billing function settings. If [Not apportion] is set for standby electric energy, then the "0"
is not a problem.
2. On the Initial Setting Tool, select [Billing Function Settings] > [Billing Function] to check the settings for
"Outdoor unit standby electric energy" mode and "Indoor unit standby electric energy" mode. If [Not
apportion] is set, the value will be "0".
3. On the Initial Setting Tool, select [Billing Function Settings] > [Outdoor Unit] or [Indoor Unit] to check that
there is a numeric value entered in the standby electric energy field.
* If you want to change the settings, give careful thought to factors such as the operation method before proceeding.
WT07442X02
124