collectively or by the groups.
Select [On individual group] to allow the operator to turn on or off the general equipment by the groups.
Select [No operations (Monitor only)] to disallow the operator to turn on or off the general equipment.
9. When [General Equipment (via PAC-YG66DCA)] is selected, in "Monitor", select which status will be used
to reflect the units' ON/OFF status to the unit icons on the Condition List screen, accessible via the Web
Browser for System Maintenance Engineer.
Select [Output status] to use the status that is sent to the general equipment, and [Input status] to use the
status that is sent from the general equipment.
10. Click [OK] after completing the settings.
11. Click the icon in "Remote controller registration" (
12. Select the address numbers of the ME remote controllers to be registered, and click [OK].
Note
• Each group can contain up to two ME remote controllers.
• Each group can contain up to four ME remote and system controllers combined.
• MA remote controllers do not need to be registered to a group.
13. Click the icon in "System controller registration" (
14. Select the address numbers of the system controllers to be registered, and click [OK].
Note
• Each group can contain up to four ME remote and system controllers combined.
15. Click the icon in "AHC registration" (
16. Select the address number of the AHC to be registered, and click [OK].
Note
• Each group can contain one AHC.
17. Click [Save] to save the settings.
Note
• Switch the "Target centralized controller" setting to make group settings for each centralized controller.
• The controllers to which [AE-200 (Billing)] or [AE-200 (No M-NET)] is set in section 6-5-1 "System
Configuration settings" will not be displayed in "Target centralized controller".
• Up to six general equipment can be registered for each DIDO controller (PAC-YG66DCA). Each contact
counts as one unit.
• Each group can contain up to 16 general equipment. (Each contact counts as one unit.)
• To change the registered units to general equipment in the group to which air conditioners, LOSSNAYs, Air
To Water (PWFY) units, HWHP (CAHV, CRHV) units, or LOSSNAYs with heater/humidifier are registered,
unregister the air conditioners, LOSSNAYs, Air To Water (PWFY) units, HWHP (CAHV, CRHV) units, or
LOSSNAYs with heater/humidifier first.
• General equipment groups cannot include remote controllers or system controllers.
WT07442X02
) to display the unit address selection screen.
) to display the unit address selection screen.
) to display the unit address selection screen.
75