Directional Comparison Pickup; Unblocking With Z1B - Siemens SIPROTEC 7SA6 Manual

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

Functions
FCT Weak Infeed
2501
OFF
„1"
ECHO only
ECHO and TRIP
Dist. OFF/BLOCK
&
O/C VTsec lost
&
O/C OFF/BLOCK
Dis. PICKUP
O/C PICKUP
from rec. logic (Figure
6-58 or 6-60)
4040
>Dis.T.BlkEcho
CB open (3pole)
Figure 6-67
Logic diagram of the echo function with distance protection teleprotection
6.6.2
Applying the Function Parameter Settings
General
6-114
Echo release by earth fault
(refer also to Figure 6-86)
≥1
≥1
≥1
S
Q
&
R
The distance protection teleprotection supplement is only in service if it is set during
the configuration to one of the possible modes of operation in address 121 . Depend-
ing on this configuration setting, only those parameters that are relevant to the select-
ed mode of operation will appear here. If the teleprotection supplement is not required,
address 121 is Teleprot. Dist. = Disabled .
The following teleprotection schemes are available:
− PUTT (Pickup)
− PUTT
− POTT
− Directional
Comparison
Pickup
− Unblocking
− Blocking
protection
2502 Time DELAY
≥1
T
&
&
&
Q
R
= Permissive underreach transfer trip with pickup, as re-
ferred to in Subsubsection 6.6.1.1,
= Permissive underreach transfer trip with zone accelera-
tion Z1B, as referred to in Subsubsection 6.6.1.2,
= Permissive overreach transfer trip, as referred to in Sub-
subsection 6.6.1.4,

= Directional comparison pickup,

as referred to in Subsubsection 6.6.1.5,
= Unblocking with Z1B, as referred to in Sub-section
6.6.1.6,
= Blocking scheme, as referred to in Sub-section 6.6.1.7,
2503 Trip EXTENSION
0
≥1
4246
T
20
0
S
ms
&
C53000-G1176-C156-2
ECHO SIGNAL
7SA6 Manual