Control During Operation
7.1.2.2

Resetting and Setting the Switching Statistics

From the
DeviceFront
:
From PC with
®
DIGSI
4
7-14
Figure 7-16
List of statistic values in DIGSI
The memories and counters for switching statistics are secured against a loss of pow-
er supply voltage. The values can, however, be set to zero, or to any desired value
within certain setting limits.
In the STATISTIC (see previous subsection) sub-menu (see previous subsection),
select the value to be set by using the
7-17 for an example of changing the trip counter. After a password is entered, the cur-
sor blinks and the number value is highlighted in a box. The number can be overwritten
using the number keys. If the new value is outside of the allowable range, either above
or below, then the maximum or minimum limit value appears at the bottom edge of the
screen. Confirm the change with the
STATISTICS
---------------------
IL3=
å
Trip Count=
Figure 7-17
Setting statistics values from the device front — example
In the Statistic window (see previous sub-section), mark the value that is to be set.
With the right mouse button, open a context menu and select Set . See Figure 7-18.
After the password for individual settings is entered, the previous value in the window
can be overwritten.
®
4 — example
key, and then press the
key.
ENTER
08/08
214.53kA
>34
ENTER
ENTER
key. See Figure
ENTER
Trip Count=
Oper. Hrs.= 3420000
34
Max
2147483648
C53000-G1176-C156-2
7SA6 Manual