Siemens SIPROTEC 7SA6 Manual page 809

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

Addr.
Setting Title
1601
PROGAM U/I
1602
DELAY FORW. PU Distance protec-
1603
DEL. NON-DIR PU Distance protec-
1610
Iph>>
1611
Iph>
1612
Uph-e (I>>)
1613
Uph-e (I>)
1614
Uph-ph (I>>)
1615
Uph-ph (I>)
1616
Iphi>
1617
Uph-e (Iphi>)
1618
Uph-ph (Iphi>)
EFFECT ϕ
1619A
ϕ >
1620
ϕ <
1621
1630A
1ph FAULTS
2002
P/S Op. mode
2006
PowerSwing trip
2101
FCT Telep. Dis.
2102
Type of Line
7SA6 Manual
C53000-G1176-C156-2
Function
Setting Options
Distance protec-
Ph-E: Uphe/ Ph-Ph: Uphph
tion, general set-
Ph-E: Uphph/Ph-Ph: Uphph
tings
Ph-E: Uphe/Ph-Ph: Uphe
Ph-E: Uphe/Ph-Ph: I>>
0.00..30.00 sec; ∞
tion, general set-
tings
0.00..30.00 sec; ∞
tion, general set-
tings
Distance protec-
0.25..10.00 A
tion, general set-
tings
Distance protec-
0.10..4.00 A
tion, general set-
tings
Distance protec-
20..70 V
tion, general set-
tings
Distance protec-
20..70 V
tion, general set-
tings
Distance protec-
40..130 V
tion, general set-
tings
Distance protec-
40..130 V
tion, general set-
tings
Distance protec-
0.10..8.00 A
tion, general set-
tings
Distance protec-
20..70 V
tion, general set-
tings
Distance protec-
40..130 V
tion, general set-
tings
Distance protec-
forward and reverse
tion, general set-
Forward
tings
30..60 °
Distance protec-
tion, general set-
tings
90..120 °
Distance protec-
tion, general set-
tings
Distance protec-
phase-earth
tion, general set-
phase to phase only
tings
Power Swing
all zones blocked
Z1/Z1B blocked
Z2 to Z5 blocked
Z1,Z1B,Z2 blocked
Power Swing
NO
YES
Teleprotection for
ON
Distance prot.
PUTT (Z1B acceleration)
POTT
OFF
Teleprotection for
Two Terminals
Distance prot.
Three Terminals
Default Setting
Ph-E: Uphe/ Ph-Ph: Uphph
Pickup program U/I
1.20 sec
Trip delay for Forward-PIKKUP
1.20 sec
Trip delay for non-directional PICKUP
1.80 A
Iph>> Pickup (overcurrent)
0.20 A
Iph> Pickup (minimum current)
48 V
Undervoltage (ph-e) at Iph>>
48 V
Undervoltage (ph-e) at Iph>
80 V
Undervoltage (ph-ph) at Iph>>
80 V
Undervoltage (ph-ph) at Iph>
0.50 A
Iphi> Pickup (minimum current at phi>)
48 V
Undervoltage (ph-e) at Iphi>
80 V
Undervoltage (ph-ph) at Iphi>
forward and reverse
Effective direction of phi-pickup
50 °
PHI> pickup (lower setpoint)
110 °
PHI< pickup (upper setpoint)
phase-earth
1ph-pickup loop selection (PU w/o
earth)
all zones blocked
Power Swing Operating mode
NO
Power swing trip
ON
Teleprotection for Distance prot. is
Two Terminals
Type of Line
Appendix
Comments
B-9