5th to 8th
reclosure cycles

6.14.3 Settings

Addr.
Setting Title
3401
AUTO RECLOSE
3402
CB? 1.TRIP
3403
T-RECLAIM
3404
T-BLOCK MC
3406
EV. FLT. RECOG.
7SA6 Manual
C53000-G1176-C156-2
Address 3466 2.AR Tdead 3Flt ; dead time after 3-phase starting
Address 3467 2.AR Tdead1Trip ; dead time after 1-pole tripping
Address 3468 2.AR Tdead3Trip ; dead time after 3-pole tripping
Address 3469 2.AR: Tdead EV. ; dead time in case of sequential fault
Address 3470 2.AR: CB? CLOSE ; check CB ready before reclosure
Address 3471 2.AR SynRequest ; sync. check after 3-pole tripping
For the 3rd cycle:
Address 3472 3.AR: START ; determines if starting in 3rd cycle is allowed at all
Address 3473 3.AR: T-ACTION ; action time for the 3rd cycle
Address 3475 3.AR Tdead 1Flt ; dead time after 1-phase starting
Address 3476 3.AR Tdead 2Flt ; dead time after 2-phase starting
Address 3477 3.AR Tdead 3Flt ; dead time after 3-phase starting
Address 3478 3.AR Tdead1Trip ; dead time after 1-pole tripping
Address 3479 3.AR Tdead3Trip ; dead time after 3-pole tripping
Address 3480 3.AR: Tdead EV. ; dead time in case of sequential fault
Address 3481 3.AR: CB? CLOSE ; check CB ready before reclosure
Address 3482 3.AR SynRequest ; sync. check after 3-pole tripping
For the 4th cycle:
Address 3483 4.AR: START ; determines if starting in 4th cycle is allowed at all
Address 3484 4.AR: T-ACTION ; action time for the 4th cycle
Address 3486 4.AR Tdead 1Flt ; dead time after 1-phase starting
Address 3487 4.AR Tdead 2Flt ; dead time after 2-phase starting
Address 3488 4.AR Tdead 3Flt ; dead time after 3-phase starting
Address 3489 4.AR Tdead1Trip ; dead time after 1-pole tripping
Address 3490 4.AR Tdead3Trip ; dead time after 3-pole tripping
Address 3491 4.AR: Tdead EV. ; dead time in case of sequential fault
Address 3492 4.AR: CB? CLOSE ; check CB ready before reclosure
Address 3493 4.AR SynRequest ; sync. check after 3-pole tripping
If more than 4 cycles have been selected during the configuration of the scope of func-
tions (section 5.1), the cycles following the fourth cycle operate with the same settings
as the fourth cycle.
Addresses which have an „A" attached to its end can only be changed with DIGSI
in " Additional Settings ".
Setting Options
OFF
ON
YES
NO
0.50..300.00 sec
0.50..300.00 sec; 0
with Pickup
with Trip
Default Setting
ON
Auto-Reclose function
NO
CB ready interrogation at 1st trip
3.00 sec
Reclaim time after successful
AR cycle
1.00 sec
AR blocking duration after
manual close
with Trip
Evolving fault recognition
Functions
®
4
Comments
6-211