Siemens SIPROTEC 7SA6 Manual page 821

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

Addr.
Setting Title
4505A
PROT 1 T-DELAY
4509
T-DATA DISTURB
4510
T-DATAFAIL
4511
Td ResetRemote
4701
ID OF RELAY 1
4702
ID OF RELAY 2
4703
ID OF RELAY 3
4710
LOCAL RELAY
5001
20 mA (B1) =
5002
20 mA (B1) =
5003
20 mA (B1) =
5004
20 mA (B1) =
5006
MIN VALUE (B1)
5007
NEG VALUE (B1)
5008
OVERFLOW (B1)
5009
Tmax OUTPUT(B1) AnalogOutputs
5011
20 mA (B2) =
5012
20 mA (B2) =
5013
20 mA (B2) =
5014
20 mA (B2) =
5016
MIN VALUE (B2)
5017
NEG VALUE (B2)
5018
OVERFLOW (B2)
5019
Tmax OUTPUT(B2) AnalogOutputs
5021
20 mA (D1) =
5022
20 mA (D1) =
5023
20 mA (D1) =
5024
20 mA (D1) =
5026
MIN VALUE (D1)
5027
NEG VALUE (D1)
5028
OVERFLOW (D1)
5029
Tmax OUTPUT(D1) AnalogOutputs
5031
20 mA (D2) =
5032
20 mA (D2) =
5033
20 mA (D2) =
5034
20 mA (D2) =
5036
MIN VALUE (D2)
5037
NEG VALUE (D2)
5038
OVERFLOW (D2)
7SA6 Manual
C53000-G1176-C156-2
Function
Setting Options
Protection Interface
0.1..30.0 ms
(Port D+E)
Protection Interface
0.05..2.00 sec
(Port D+E)
Protection Interface
0.0..60.0 sec
(Port D+E)
0.00..300.00 sec; ∞
Protection Interface
(Port D+E)
Protection Interface
1..65534
(Port D+E)
Protection Interface
1..65534
(Port D+E)
Protection Interface
1..65534
(Port D+E)
Protection Interface
relay 1
(Port D+E)
relay 2
relay 3
AnalogOutputs
10.0..1000.0 %
AnalogOutputs
10..100000 A
AnalogOutputs
1.0..1000.0 km
AnalogOutputs
1.0..1000.0 Miles
AnalogOutputs
0.0..5.0 mA
AnalogOutputs
1.00..22.50 mA
AnalogOutputs
1.00..22.50 mA
0.10..180.00 sec; ∞
AnalogOutputs
10.0..1000.0 %
AnalogOutputs
10..100000 A
AnalogOutputs
1.0..1000.0 km
AnalogOutputs
1.0..1000.0 Miles
AnalogOutputs
0.0..5.0 mA
AnalogOutputs
1.00..22.50 mA
AnalogOutputs
1.00..22.50 mA
0.10..180.00 sec; ∞
AnalogOutputs
10.0..1000.0 %
AnalogOutputs
10..100000 A
AnalogOutputs
1.0..1000.0 km
AnalogOutputs
1.0..1000.0 Miles
AnalogOutputs
0.0..5.0 mA
AnalogOutputs
1.00..22.50 mA
AnalogOutputs
1.00..22.50 mA
0.10..180.00 sec; ∞
AnalogOutputs
10.0..1000.0 %
AnalogOutputs
10..100000 A
AnalogOutputs
1.0..1000.0 km
AnalogOutputs
1.0..1000.0 Miles
AnalogOutputs
0.0..5.0 mA
AnalogOutputs
1.00..22.50 mA
AnalogOutputs
1.00..22.50 mA
Default Setting
30.0 ms
Prot 1: Maximal permissible delay time
0.10 sec
Time delay for data disturbance alarm
6.0 sec
Time del for transmission failure alarm
0.00 sec
Remote signal RESET DELAY for
comm.fail
1
Identification number of relay 1
2
Identification number of relay 2
3
Identification number of relay 3
relay 1
Local relay is
200.0 %
20 mA (B1) correspond to
20000 A
20 mA (B1) correspond to
50.0 km
20 mA (B1) correspond to
50.0 Miles
20 mA (B1) correspond to
4.0 mA
Output value (B1) valid from
19.84 mA
Output value (B1) for negative values
22.50 mA
Output value (B1) for overflow
5.00 sec
Maximum output time (B1)
200.0 %
20 mA (B2) correspond to
20000 A
20 mA (B2) correspond to
50.0 km
20 mA (B2) correspond to
50.0 Miles
20 mA (B2) correspond to
4.0 mA
Output value (B2) valid from
19.84 mA
Output value (B2) for negative values
22.50 mA
Output value (B2) for overflow
5.00 sec
Maximum output time (B2)
200.0 %
20 mA (D1) correspond to
20000 A
20 mA (D1) correspond to
50.0 km
20 mA (D1) correspond to
50.0 Miles
20 mA (D1) correspond to
4.0 mA
Output value (D1) valid from
19.84 mA
Output value (D1) for negative values
22.50 mA
Output value (D1) for overflow
5.00 sec
Maximum output time (D1)
200.0 %
20 mA (D2) correspond to
20000 A
20 mA (D2) correspond to
50.0 km
20 mA (D2) correspond to
50.0 Miles
20 mA (D2) correspond to
4.0 mA
Output value (D2) valid from
19.84 mA
Output value (D2) for negative values
22.50 mA
Output value (D2) for overflow
Appendix
Comments
B-21