Settings - Siemens SIPROTEC 7SA6 Manual

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

Functions
6.8.3

Settings

Addr.
Setting Title
3201
FCT Telep. E/F
3202
Line Config.
3203A
Send Prolong.
3207A
Delay for alarm
3208
Release Delay
3209A
TrBlk Wait Time
3210A
TrBlk BlockTime
6-154
Addresses which have an „A" attached to its end can only be changed with DIGSI
in " Additional Settings ".
Setting Options
ON
OFF
Two Terminals
Three Terminals
0.00..30.00 sec
0.00..30.00 sec
0.000..30.000 sec
0.00..30.00 sec; ∞
0.00..30.00 sec
Default Setting
ON
Teleprotection for Earth Fault O/
C
Two Terminals
Line Configuration
0.05 sec
Time for send signal prolonga-
tion
10.00 sec
Unblocking: Time Delay for
Alarm
0.000 sec
Time Delay for release after pik-
kup
0.04 sec
Transient Block.: Duration exter-
nal flt.
0.05 sec
Transient Block.: Blk.T. after ext.
flt.
®
4
Comments
7SA6 Manual
C53000-G1176-C156-2