Siemens SIPROTEC 7SA6 Manual page 569

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

7.4.5
Tagging
:
From PC with
®
DIGSI
4
MAIN MENU
--------------------
Annunciation
Measurement
Control
Figure 7-56
Tagging Equipment from the HMI
7SA6 Manual
C53000-G1176-C156-2
To identify unusual operating conditions in the power system, tagging can be done.
The tagging can, for example, be entered as additional operating conditions in inter-
locking checks, which are set up with CFC. Tagging is configured in the same way as
for operating devices.
With a device ready for operation, first press the
key, select the menu item Control and move to editing the control func-
Using the
key. The selection CONTROL appears.
tions with the
Select the item Tagging with the
key. The selection TAGGING appears. See Figure 7-56. The status of the tagging
is displayed Tagging → Display , or changed using Tagging → Set .
03/05
–>
1
–>
2
–>
3
CONTROL
---------------------
Breaker/Switch
Tagging
Interlock
Note:
The Manual Overwrite function is always done using the HMI on the SIPROTEC
devices.
Control During Operation
key. The MAIN MENU appears.
MENU
key and switch to the next selection using the
02/03
–>
1
–>
2
TAGGING
---------------------
–>
3
Display
Set
01/02
–>
1
–>
2
®
4
7-55