Manual Overwrite / Tagging

Manual Overwrite
Set Status
Tagging
MAIN MENU
--------------------
Annunciation
Measurement
Control
Figure 4-11
Tagging equipment from the operator control panel
4-16
If the breaker/switch position is not available from the switch-gear, the status of the
switchgear device can be manually set to the actual present position using the opera-
tor control panel: Main Menu → Control → Breaker/Switch → Man. Over-
write. The simulated switching status is used for interlocking checks, and for auto-
matically initiated switching operations.
For convenience during commissioning or at other times, decoupling of the informa-
tion exchange between the switchgear and the protective device may be desired for a
short period, without disconnecting the wires. This function is activated using the op-
erator control panel: Main Menu → Control → Breaker/Switch → Set Status.
To identify unusual operating conditions in the power system, tagging can be done.
The tagging can, for example, be entered as additional operating conditions in inter-
locking checks, which are set up with CFC. Tagging is configured in the same way as
for operating devices.
• The status of the tagging is displayed on the operating panel, Main Menu → Con-
trol → Tagging → Display (Figure 4-11),
or changed using
• Main Menu → Control → Tagging → Set.
03/05
–>
1
–>
2
–>
3
CONTROL
---------------------
Breaker/Switch
Tagging
Interlock
Note:
The Manual Overwrite function is always done using the operator control panel on the
®
SIPROTEC
4 devices.