Siemens SIPROTEC 7SA6 Manual page 317

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

Direction
Determination with
Negative Sequence
System
Blocking
Switching onto an
Earth Fault
7SA6 Manual
C53000-G1176-C156-2
„Reverse"
Figure 6-74
Directional characteristic using I
For the determination of direction a minimum current I
quantity is required. The minimum polarizing voltage set as 3U0> . If the displacement
voltage is too small, the direction can only be determined if it is polarized with the
transformer star-point current and this exceeds a minimum value corresponding to the
setting IY> . The direction determination with U
transformer mcb is reported via binary input.
It is advantageous to use negative sequence system values for the direction measure-
ment if the resulting zero sequence voltages during earth faults are too small for an
accurate measurement or when the zero sequence values are subject to interference
by for example mutual coupling from a parallel line.
Otherwise this function operates the same as the direction measurement with zero se-
quence current and zero sequence voltage. The negative sequence signals 3 I
3U
are simply used instead of the signals 3 I
2
a minimum magnitude of 3I2> or 3U2> .
The earth fault protection can be blocked by the distance protection. If in this case a
fault is detected by the distance protection, the earth fault protection will not operate.
This gives the selective fault clearance by the distance protection preference over trip-
ping by the earth fault protection.
The earth fault protection can also be blocked during the single-pole dead time of an
automatic reclose cycle. This prevents an incorrect measurement resulting from the
zero sequence current and voltage signals arising in this state. If the device is com-
bined with an external automatic reclose device or if single-pole tripping can result
from a separate (parallel tripping) protection device, the earth fault protection must be
blocked via binary input during the single-pole open condition.
To achieve fast tripping following manual closure of the circuit breaker on to an earth
fault, the manual close command from the control switch can be routed to the device
via a binary input. The earth fault protection can then trip three-pole without delay. The
stage(s) that should be activated for instantaneous tripping after manual closure can
be selected with setting parameters. (refer to logic diagrams Figure 6-69 to 6-71).
Im
U
P
β
β
U
= 122°
E
α
α
= –22°
as polarization quantity
Y
E
und 3U
0
j76°
k
e
I
Y
Y
„Forward"
= 3U
0
I
E
and a minimum polarization
E
is inhibited when a trip of the voltage
. These signals must also have
0
Functions
Re
und
2
6-127

Advertisement

Table of Contents
loading

Table of Contents