Siemens SIPROTEC 7SA6 Manual page 215

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

6.1.3.1
Settings
Addr.
Setting Title
1103
FullScaleVolt.
1104
FullScaleCurr.
1105
Line Angle
1110
x'
1111
Line Length
1112
x'
1113
Line Length
1116
RE/RL(Z1)
1117
XE/XL(Z1)
7SA6 Manual
C53000-G1176-C156-2
~
Multiple fault on a double-circuit line next to a generato
Figure 6-14
Address 1156A Trip2phFlt determines that the short-circuit protection functions
perform only a single-pole trip in case of isolated two-phase faults (clear of ground),
provided that single-pole tripping is possible and permitted. This allows a single-pole
rapid automatic reclosure cycle for this kind of fault. The trip type can be set to 1pole
leading phase or 1pole lagging phase. The parameter is only available in ver-
sions with single-pole tripping. This setting can only be modified with DIGSI
"Additional Settings". If this option is used, it must be born in mind that the phase
preference should be the same throughout the entire network and that it must be the
same at all ends of one line. More information on the function is also contained in Sec-
tion 6.22.3 Overall Fault Detection Logic of the Device. The default setting is triple-
pole.
Note: The indicated secondary current values and values of impedance for setting
ranges and default settings refer to I
values are to be multiplied by 5. The values of impedance are divided by 5.
Addresses which have an „A" attached to its end can only be changed with DIGSI
in "Additional Settings".
Setting Options
1.0..1200.0 kV; 0
10..5000 A
30..89 °
0.0050..6.5000 Ohm / km
1.0..1000.0 km
0.0050..10.0000 Ohm / mile
0.6..650.0 Miles
-0.33..7.00
-0.33..7.00
L1–E
L2–E
= 1 A. For the nominal current 5 A the current
N
Default Setting
400.0 kV
1000 A
85 °
0.1500 Ohm / km
100.0 km
0.2420 Ohm / mile x' - Line Reactance per length
62.1 Miles
1.00
1.00
Functions
r
®
Comments
Measurement: Full Scale
Voltage (100%)
Measurement: Full Scale Cur-
rent (100%)
Line Angle
x' - Line Reactance per length
unit
Line Length
unit
Line Length
Zero seq. comp. factor RE/RL
for Z1
Zero seq. comp. factor XE/XL for
Z1
4 under
®
4
6-25