Point List
3.2.4

Directional time overcurrent protection

ASDU
Function
Informa-
type
tion
number
1
63
1
1
63
2
1
63
3
1
63
4
1
63
10
1
63
11
1
63
12
1
63
13
1
63
14
1
63
15
2
63
20
2
63
24
2
63
25
2
63
30
2
63
34
2
63
35
2
63
41
2
63
42
2
63
43
2
63
44
2
63
45
2
63
46
2
63
50
2
63
51
2
63
52
2
63
53
2
63
54
2
63
55
2
63
62
2
63
63
2
63
64
2
63
67
2
63
71
2
63
72
30
Name
>BLOCK 67-1
>BLOCK 67-TOC
>BLOCK 67N-1
>BLOCK 67N-TOC
67/67-TOC OFF
67 BLOCKED
67 ACTIVE
67N OFF
67N BLOCKED
67N ACTIVE
67-1 picked up
67-1 Time Out
67-1 TRIP
67-TOC pickedup
67-TOC Time Out
67-TOC TRIP
67N-1 picked up
67N-1 Time Out
67N-1 TRIP
67N-TOCPickedup
67N-TOC TimeOut
67N-TOC TRIP
67/67N pickedup
67 A picked up
67 B picked up
67 C picked up
67N picked up
67/67N TRIP
67N-2 picked up
67N-2 Time Out
67N-2 TRIP
67-2 picked up
67-2 Time Out
67-2 TRIP
Description
>BLOCK 67-1; ON = 1, OFF = 0
>BLOCK 67-TOC; ON = 1, OFF = 0
>BLOCK 67N-1; ON = 1, OFF = 0
>BLOCK 67N-TOC; ON = 1, OFF = 0
67/67-TOC switched OFF; ON = 1, OFF = 0
67/67-TOC is BLOCKED; blocked = 1, unblocked = 0
67/67-TOC is ACTIVE; activate = 1, deactivate = 0
67N/N67-TOC switched OFF; ON = 1, OFF = 0
67N/67N-TOC is BLOCKED; blocked = 1, unblocked = 0
67N/67N-TOC is ACTIVE; activate = 1, deactivate = 0
67-1 picked up; ON = 1, OFF = 0
67-1 Time Out; ON = 1, OFF = 0
67-1 TRIP; ON = 1, OFF = 0
67-TOC picked up; ON = 1, OFF = 0
67-TOC Time Out; ON = 1, OFF = 0
67-TOC TRIP; ON = 1, OFF = 0
67N-1 picked up; ON = 1, OFF = 0
67N-1 Time Out; ON = 1, OFF = 0
67N-1 TRIP; ON = 1, OFF = 0
67N-TOC picked up; ON = 1, OFF = 0
67N-TOC Time Out; ON = 1, OFF = 0
67N-TOC TRIP; ON = 1, OFF = 0
67/67N picked up; ON = 1, OFF = 0
67/67-TOC Phase A picked up; ON = 1, OFF = 0
67/67-TOC Phase B picked up; ON = 1, OFF = 0
67/67-TOC Phase C picked up; ON = 1, OFF = 0
67N/67N-TOC picked up; ON = 1, OFF = 0
67/67N TRIP; ON = 1, OFF = 0
67N-2 picked up; ON = 1, OFF = 0
67N-2 Time Out; ON = 1, OFF = 0
67N-2 TRIP; ON = 1, OFF = 0
67-2 picked up; ON = 1, OFF = 0
67-2 Time Out; ON = 1, OFF = 0
67-2 TRIP; ON = 1, OFF = 0
2621
2622
2623
2624
2651
2652
2653
2656
2657
2658
2660
2664
2665
2670
2674
2675
2681
2682
2863
2684
2685
2686
2691
2692
2693
2694
2695
2696
2646
2648
2679
2642
2647
2649
7SJ61 / 7SJ62 / 7SJ64 Bus mapping
C53000-L2540-A306-2
Obj. -
Adr.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sj62Siprotec 7sj64

Table of Contents