7.1.2

Switching Statistics

7.1.2.1

Viewing the Switching Statistics

From the
DeviceFront
:
From PC with
®
DIGSI
4
7SA6 Manual
C53000-G1176-C156-2
The messages in switching statistics are counters for the accumulation of interrupted
currents by each of the breaker poles, the number of trips issued by the device to the
breaker. The interrupted currents are in primary terms.
Switching statistics can be viewed on the LCD of the device, or on a PC running
®
DIGSI
4 and connected to the operating or service interface.
A password is not required to read switching statistics; however, a password is re-
quired to change or delete the statistics.
In 7SA6 the statistics register the data of the protection communication. The transmis-
sion time of the information from device to device via protection data interfaces (com-
ing and going) is measured steadily and registered in the folder "Statistic". The avail-
bility of the means of transmission is also indicated. The availability is indicated in %/
min and %/h. This enables the user to assess the transmission quality.
For each trip command initiated by a protective element of the device, the magnitude
of interrupted current for each circuit breaker pole is determined and stored. The cur-
rent magnitudes are added to previously interrupted currents, and the accumulated
values are stored.
In devices with automatic reclosure the number of reclosure commands is counted,
i. e. separately according to single-pole (if available) and three-pole automatic reclos-
ure cycles as well as separately according to the first and all further automatic reclos-
ures.
The memories are protected against auxiliary voltage failure.
With a device ready for operation, first press the
The first menu item Annunciation is marked.
key to enter the ANNUNCIATION sub-menu (see Figure 7-1).
Press the
key to select the item Statistic , and switch to the list of statistics values
Use the
key. The STATISTIC list appears. See Figure 7-15.
using the
STATISTICS
---------------------
Σ IL1=
Σ IL2=
Etc.
Figure 7-15
Switching statistics viewed from the front display
Under Annunciation (Figure 7-2), the switching statistics can be found by double
clicking. Double click on Statistic . The contents of the statistic counters is dis-
played in another window. See Figure 7-16.
MENU
1/05
0.00kA
0.00kA
Control During Operation
key. The MAIN MENU appears.
— example
7-13