Read-Out Of Information; Messages; Output Of Messages - Siemens SIPROTEC 7SA6 Manual

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

Control During Operation
7.1

Read-out of Information

General
7.1.1

Messages

7.1.1.1

Output of Messages

Light-Emitting
Diodes
7-2
The device provides a great deal of information that can be obtained on-site or from
data transfer:
• Messages,
• Operating measurement and metered values,
• Waveform data in oscillographic fault records.
This information is individually discussed below. Methods for viewing, retrieving, ac-
knowledging, and storing this information on a PC are also explained.
Messages provide operating information about the power system, the device, and the
measurements. Other messages give an overview of important events such a network
fault and the operation of device functions. The information provided is useful in
checking overall operation of the device during testing and commissioning.
Password entry is not required to read messages.
The messages generated in the device can be presented in various ways:
• Display using light-emitting diodes (LEDs) on the front of the device,
• Operation of output relays connected to external signalling equipment,
• Display in the LCD on the front of the device,
• Display on the screen of a PC running the DIGSI
erating or service interface of the device,
• Transfer to a master station using one of the serial system interfaces (if available).
The green light-emitting diode with the label "RUN" lights continuously during normal
operation.
The red LED with the label "ERROR" indicates that the processor system has recog-
nized an internal problem. If this LED lights up, then the device is not operational.
Chapter 9 discusses steps to take if a failure occurs in the device.
The other LEDs on the front of the device display the messages in accordance with
the configuration, as discussed in Chapter 5. The description of each LED illumination
should then be indicated on the label strips.
If the messages for the LEDs are latched, then the memory can be reset with the LED
key
. This key simultaneously serves as a functional check for all of the LEDs ex-
LED
cept the "RUN" and "ERROR" LEDs. While the key is pressed, all of these LEDs must
light.
LEDs that display a condition should light for as long as the condition is maintained.
The LED action is therefore generally not latched. Of course, these LEDs are also in-
cluded in the function check with the LED key
®
4 program, connected to the op-
.
LED
C53000-G1176-C156-2
7SA6 Manual

Advertisement

Table of Contents
loading

Table of Contents