Siemens SIPROTEC 7SA6 Manual page 531

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

7SA6 Manual
C53000-G1176-C156-2
Tabelle 7-2
Operating measured values transmitted from the other end via protection data
interface in comparison with the local operating measured values
Geräte ADR
device address of the remote device
I
, I
, I
remote
phase currents of the remote device
L1
L2
L3
I
, I
, I
local
phase currents of the local device
L1
L2
L3
ϕ(I
), ϕ(I
), ϕ(I
)
phase angles between remote and
L1
L2
L3
local phase currents
U
, U
, U
remote
voltages of remote device
L1
L2
L3
U
, U
, U
local
voltages of local device
L1
L2
L3
ϕ(U
), ϕ(U
), ϕ(U
) phase angles between remote and
L1
L2
L3
local voltages
1
) for lines acc. to address 1104 (refer to Subsection 6.1.3),
2
) acc. to address 1103 (refer to Subsection 6.1.3)
If the device is provided with analog outputs allocated to certain measured values dur-
ing the configuration according to Section 5.1, they can be read out in the display (e.g.
analog instrument).
Except for the current measured values the user can also read out the minimum, max-
imum and long-term measured values. The interval range for the calculation of the av-
erage value was set in Subsection 6.23.4.
The following average values are available:
• I
dmd, I
dmd, I
dmd, I
L1
L2
L3
positive sequence system;
• Pdmd, Pdmd Forw, Pdmd Rev: the active power as a whole and separately accord-
ing to Demand Forward and Demand Reverse;
• Qdmd, QdmdForw, QdmdRev: the reactive power as a whole and separately ac-
cording to Demand Forward and Demand Reverse;
• Sdmd: the apparent power.
For the following values both the minimum and the maximum values are available:
• I
, I
, I
, I
: phase currents and the positive sequence current;
L1
L2
L3
1
• I
d, I
d, I
d, I
d: average values of the phase currents and the positive sequence
L1
L2
L3
1
current;
• U
, U
, U
, U
L1–E
L2–E
L3–E
• U
, U
, U
L1–L2
L2–L3
L3–L1
• PForw, PRev, QForw, QRev, S: active and reactive power separately according to
Demand Forward and Demand Reverse as well as apparent power;
• Pd, Qd, Sd: average values of active, reactive and apparent power;
Data
dmd: the measured values of the phase currents and
1
: phase-earth voltages and positive sequence voltage;
1
, 3U
: phase-phase voltages and zero sequence voltage;
0
Control During Operation
prim. value
(absolute)
operating nominal current
operating nominal current
°
operating nominal voltage
√ 3
2
)
operating nominal voltage
√ 3
2
)
°
7-17