From PC with
®
DIGSI
4
Figure 7-24
Set Points in DIGSI
7SA6 Manual
C53000-G1176-C156-2
Set points are only available in online–mode. The metered value groups are to be
found under Measurement (Figure 7-2) by double-clicking on the latter. Select Other
and then Set Points (Measured Values)( Figure 7-24).
By double clicking on an entry in the list in the right part of the window, the set points
are loaded. Mark the number of the value which is to be changed. With a right mouse
click, open the context menu and click on Set, as shown in Figure 7-24. A password
inquiry (password No 5 for individual settings) occurs. Next, the dialog field Set Me-
tered Value is opened. Enter the desired value in the entry field. Then click on OK .
The entered value is transferred to the device and the display within the window in Fig-
ure 7-24 is updated.
®
4
Control During Operation
7-23