Siemens SIPROTEC 7SA6 Manual page 326

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

Functions
Addr.
Setting Title
3123
3I0>> Telep/BI
3124
3I0>> SOTF-Trip
3125
3I0>> InrushBlk
3130
Op. mode 3I0>
3131
3I0>
3131
3I0>
3132
T 3I0>
3133
3I0> Telep/BI
3134
3I0> SOTF-Trip
3135
3I0> InrushBlk
3140
Op. mode 3I0p
3141
3I0p PICKUP
3141
3I0p PICKUP
3147
Add.T-DELAY
3148
3I0p Telep/BI
3149
3I0p SOTF-Trip
3150
3I0p InrushBlk
3142
3I0p MinT-DELAY
3143
3I0p Time Dial
3144
3I0p Time Dial
3145
3I0p Time Dial
3146
3I0p MaxT-DELAY
3151
IEC Curve
6-136
Setting Options
NO
YES
NO
YES
NO
YES
Forward
Reverse
Non-Directional
Inactive
0.05..25.00 A
0.003..25.000 A
0.00..30.00 sec; ∞
NO
YES
NO
YES
NO
YES
Forward
Reverse
Non-Directional
Inactive
0.05..25.00 A
0.003..25.000 A
0.00..30.00 sec; ∞
NO
YES
NO
YES
NO
YES
0.00..30.00 sec
0.05..3.00 sec; ∞
0.50..15.00; ∞
0.05..15.00 sec; ∞
0.00..30.00 sec
Normal Inverse
Very Inverse
Extremely Inverse
Long time inverse
Default Setting
NO
Instantaneous trip via Teleprot./
BI
NO
Instantaneous trip after Swit-
chOnToFault
NO
Inrush Blocking
Inactive
Operating mode
1.00 A
3I0> Pickup
1.000 A
3I0> Pickup
0.90 sec
T 3I0> Time Delay
NO
Instantaneous trip via Teleprot./
BI
NO
Instantaneous trip after Swit-
chOnToFault
NO
Inrush Blocking
Inactive
Operating mode
1.00 A
3I0p Pickup
1.000 A
3I0p Pickup
1.20 sec
Additional Time Delay
NO
Instantaneous trip via Teleprot./
BI
NO
Instantaneous trip after Swit-
chOnToFault
NO
Inrush Blocking
1.20 sec
3I0p Minimum Time Delay
0.50 sec
3I0p Time Dial
5.00
3I0p Time Dial
1.35 sec
3I0p Time Dial
5.80 sec
3I0p Maximum Time Delay
Normal Inverse
IEC Curve
Comments
7SA6 Manual