Siemens SIPROTEC 7SA6 Manual page 807

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

Addr.
Setting Title
ϕ load (Ø-Ø)
1244
1301
Op. mode Z1
1302
R(Z1) Ø-Ø
1303
X(Z1)
1304
RE(Z1) Ø-E
1305
T1-1phase
1306
T1-multi-phase
1307
Zone Reduction
1311
Op. mode Z2
1312
R(Z2) Ø-Ø
1313
X(Z2)
1314
RE(Z2) Ø-E
1315
T2-1phase
1316
T2-multi-phase
1317A
Trip 1pole Z2
1321
Op. mode Z3
1322
R(Z3) Ø-Ø
1323
X(Z3)
1324
RE(Z3) Ø-E
7SA6 Manual
C53000-G1176-C156-2
Function
Setting Options
20..60 °
Distance protec-
tion, general set-
tings
Distance zones
Forward
(quadrilateral)
Reverse
Non-Directional
Inactive
Distance zones
0.050..250.000 Ohm
(quadrilateral)
Distance zones
0.050..250.000 Ohm
(quadrilateral)
Distance zones
0.050..250.000 Ohm
(quadrilateral)
0.00..30.00 sec; ∞
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
0.00..30.00 sec; ∞
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
0..45 °
Distance zones
(quadrilateral)
Distance zones
Forward
(quadrilateral)
Reverse
Non-Directional
Inactive
Distance zones
0.050..250.000 Ohm
(quadrilateral)
Distance zones
0.050..250.000 Ohm
(quadrilateral)
Distance zones
0.050..250.000 Ohm
(quadrilateral)
0.00..30.00 sec; ∞
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
0.00..30.00 sec; ∞
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
Distance protec-
NO
tion, general set-
YES
tings
Distance zones
(quadrilateral)
Distance zones
Forward
(quadrilateral)
Reverse
Non-Directional
Inactive
Distance zones
0.050..250.000 Ohm
(quadrilateral)
Distance zones
0.050..250.000 Ohm
(quadrilateral)
Distance zones
0.050..250.000 Ohm
(quadrilateral)
Default Setting
45 °
PHI load, maximum Load Angle (ph-
ph)
Forward
Operating mode Z1
1.250 Ohm
R(Z1), Resistance for ph-ph-faults
2.500 Ohm
X(Z1), Reactance
2.500 Ohm
RE(Z1), Resistance for ph-e faults
0.00 sec
T1-1phase, delay for single phase
faults
0.00 sec
T1multi-ph, delay for multi phase faults
0 °
Zone Reduction Angle (load compen-
sation)
Forward
Operating mode Z2
2.500 Ohm
R(Z2), Resistance for ph-ph-faults
5.000 Ohm
X(Z2), Reactance
5.000 Ohm
RE(Z2), Resistance for ph-e faults
0.30 sec
T2-1phase, delay for single phase
faults
0.30 sec
T2multi-ph, delay for multi phase faults
NO
Single pole trip for faults in Z2
Reverse
Operating mode Z3
5.000 Ohm
R(Z3), Resistance for ph-ph-faults
10.000 Ohm
X(Z3), Reactance
10.000 Ohm
RE(Z3), Resistance for ph-e faults
Appendix
Comments
B-7