Siemens SIPROTEC 7SA6 Manual page 469

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

FFM I< (max)
2912
I
L1
I>
I
L2
I>
I
L3
I>
3I
0
I>
3I
2
I>
0207
2911
FFM U>(min)
Isolated
Peterson-Coil
3U
0
U>
Solid Earthed
3U
2
U>
1pole dead time
Figure 6-142 Logic diagram of the fuse failure monitor with zero and negative sequence system
Fuse Failure
Monitor
(Three-Phase)
7SA6 Manual
C53000-G1176-C156-2
≥1
≥1
SystemStarpoint
≥1
≥1
A three-phase failure of the secondary measured voltage can be distinguished from
an actual system fault by the fact that the currents have no significant change in the
event of a failure in the secondary measured voltage. For this reason, the sampled
current values are routed to a buffer, so that the difference between the present and
stored current values can be analysed to recognize the magnitude of the current dif-
ferential (current differential criterion). A three-pole voltage failure is detected if
• all three phase–earth voltages are smaller than the threshold FFM U<max (3ph) ,
• the current differential in all three phases is smaller than the threshold
FFM Idelta (3p) , and
• all three phase current amplitudes are greater than the minimum current Iph> for
impedance measurement by the distance protection.
If no stored current values are present (yet), the current magnitude criterion is resorted
to. A three-pole system voltage failure is detected in this case if
• all three phase–earth voltages are smaller than the threshold FFM U<max (3ph) ,
• all three phase current amplitudes are smaller than the minimum current Iph> for
impedance measurement by the distance protection, and
• all three phase current amplitudes are greater than a fixed set noise threshold
(40 mA).
If such a voltage failure is recognized, the distance protection and all other functions
that operate on the basis of undervoltage (e.g. also weak infeed tripping, undervoltage
protection) are blocked until the voltage failure is removed; thereafter the blocking is
&
&
≥1
&
FNo 170
VT FuseFail
FNo 169
10 s
0
≥1
Fuse–Failure
Functions
6-279

Advertisement

Table of Contents
loading

Table of Contents