Binary Inputs
7SA6 Manual
C53000-G1176-C156-2
Table A-1
LED indication presettings
LED
LCD Text
LED12
AR not ready
LED13
>Door open
>CB wait
LED14
Alarm Sum Event
1
) devices with single- and three-pole tripping
2
) devices with three-pole tripping only
3
) devices with automatic reclosure
Table A-2
Binary input presettings
Binary Input
LCD Text
BI1
>Reset LED
BI2
>Manual Close
BI3
>FAIL:Feeder VT
>I-STUB ENABLE
BI4
>DisTel Rec.Ch1
BI5
>CB1 Ready
>CB wait
1
) only devices without power relays
2
) only devices with power relays
Table A-3
Further binary input presettings for 7SA610*–*B/F/K
Binary Input
LCD Text
BI6
>CB 3p Open
>CB1 3p Open
BI7
>CB 3p Closed
>CB1 3p Closed
Function No.
3
2784
)
Automatic reclosure not ready at
present, unlatched
High voltage system, door open or
CB waiting for spring charged, un-
latched
160
General alarm, unlatched
Function No.
5
Reset of LED indications,
H–active
356
Manual close of circuit breaker,
H–active
no presetting
361
Voltage transformer secondary
miniture circuit breaker, H–active
4006
Distance protection teleprotection re-
ceive signal, H–active
371
Circuit breaker 1 ready, L–active
CB waiting for spring charged,
L–active
Function No.
380
Circuit breaker position 3pole Open,
411
H-active
379
Circuit breaker position 3pole
410
Closed, H-active
Appendix
Remarks
3
)
Remarks
2
)
Remarks
A-67