Siemens SIPROTEC 7SA6 Manual page 551

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

From the
DeviceFront
:
From PC with
®
DIGSI
4
7SA6 Manual
C53000-G1176-C156-2
With a device ready for operation, first press the
key, highlight the menu item Test/Diagnose , and then press the
Using the
key to enter sub-menu. TEST/DIAGNOSE will appear at the top of the menu.
At this point, highlight the menu item Test Enable using the
key to enter sub-menu. TEST ENABLE will appear at the top of the menu. See
the
Figure 7-37.
TEST DIAGNOSE
--------------------
Device Reset
>Test Enable
Blk Data Trans–>
Hardware Test –>
Set/Reset
SIEMENS Intern
Figure 7-37
Applying Test Mode from the Operator Control Panel
To start Test mode , press the
nostics) and confirm with the
OFF . Use the
and
question " Are you sure? " is displayed. Highlight the desired response and press
key. If the mode is changed, the footer shows the message " Control Ex-
the
ENTER
ecuted " for a short time.
key to return to the TEST/DIAGNOSE level; press the
Use the
the MAIN MENU .
The procedure for changing the Block Data Transmission mode is the same. See Fig-
ure 7-38 (simplified).
TEST/DIAGNOSE
--------------------
>Blk Data Trans–>
Hardware Test –>
Figure 7-38
Applying a Block of Data Transmission from the Front Panel (simplified)
The settings for the test mode and the data transmission block are normally OFF . Def-
initions:
− Test mode – With the ON setting, the "test mode"-bit is transferred for messages
compatible with IEC 60 870–5–103.
− DataStop
– With the ON setting, no messages or measured values are trans-
ferred ("transfer block").
Click on Device in the menu bar to reach the commands Block Data Transmis-
sion and Test Mode . See Figure 7-39.
02/06
–>
1
–>
2
3
4
–> 11
12
key, enter the password N° 4 (for test and diag-
ENTER
key. A new window appears with the options ON and
ENTER
keys to select the desired mode, and press the
03/06
3
BLK DATA TRANS
4
--------------------
>DataStop
Control During Operation
key. The MAIN MENU appears.
MENU
key, and then press
TEST ENABLE
--------------------
>Test mode
ENTER
key to return to
MENU
OFF
OFF
key. The
7-37

Advertisement

Table of Contents
loading

Table of Contents