6.22.6 Applying the Function Parameter Settings

6.22.7 Settings

Fault display
Addr.
Setting Title
610
FltDisp.LED/LCD
615
Spont. FltDisp.
6-304
TRIP
CLOSE
TMin TRIP Cmd
0240
Figure 6-157 Trip/Close test cycle
The configuration concerning the tripping logic of the device as a whole and circuit-
breaker test function was already set in accordance with the general data in Subsec-
tion 6.1.3 and 6.1.1.
Furthermore, the setting in address 610 FltDisp.LED/LCD , determines whether the
fault messages which are allocated to the local LEDs as well as the spontaneous mes-
sages that are displayed via the LCD on the front of the device following a fault, are
stored following each fault detection of a protection function ( with PICKUP ), or if stor-
age only takes place if a trip command is issued ( with TRIP = "No trip no flag"-feature).
Setting Options
Display Targets on every
Pickup
Display Targets on TRIP only
NO
YES
T-CBtest-dead
TMax CLOSE CMD
0242
Default Setting
Display Targets on
every Pickup
NO
t
0241
Comments
Fault Display on LED / LCD
Spontaneous display of
flt.annunciations
7SA6 Manual
C53000-G1176-C156-2