Siemens SIPROTEC 7SA6 Manual page 581

Distance protection relay for all voltage levels
Hide thumbs Also See for SIPROTEC 7SA6:
Table of Contents

Advertisement

SIEMENS
LED
Figure 8-6
Installing a 7SA612 with a four-line display in a rack or cubicle (housing width
as an example
Panel Surface
Mounting
7SA6 Manual
C53000-G1176-C156-2
Mounting bracket
RUN
ERROR
MAIN MENU
01/04
Annunciation
1
Measurement
2
MENU
ENTER
ESC
Annunciation
F1
7
8
Meas. Val.
F2
4
5
F3
Trip log
1
2
F4
0
+/-
Mounting bracket
G
Connect the plug terminals and/or the screwed terminals on the rear side of the de-
vice according to the wiring diagram for the rack.
When using forked lugs or directly connecting wires to screwed terminals, the
screws must be tightened so that the heads are even with the terminal block before
the lugs or wires are inserted.
A ring lug must be centred in the connection chamber so that the screw thread fits
in the hole of the lug.
Section 2.1 has pertinent information regarding wire size, lugs, bending radii, etc.
G
Secure the device to the panel with four screws. For dimensions refer to Figure
10-11 to 10-13 in Section 10.22.
G
Connect the ground of the device to the protective ground of the panel. The cross-
sectional area of the ground wire must be greater than or equal to the cross-sec-
tional area of any other control conductor connected to the device. Furthermore, the
cross-section of the ground wire must be at least 2.5 mm
Connect solid, low-impedance operational grounding (cross-sectional area ≥
G
2
2.5 mm
) to the grounding surface on the side. Use at least one M4 screw for the
device ground.
G
Connections according to the circuit diagram via screw terminals, connections for
optical fibres and electrical communication modules via the inclined housings. Sec-
tion 2.2 has pertinent information regarding wire size, lugs, bending radii, etc.
9
6
3
Installation and Commissioning
SIPROTEC
7SA612
1
/
of 19 inch rack)
1
2
.
8-7