Viewing Operation-
al Messages
7SA6 Manual
C53000-G1176-C156-2
®
Figure 3-8
DIGSI
4 — Viewing the secondary operating measured values — example
A table of the secondary operating measured values appears, as shown in Figure 3-9.
Since no measured AC currents or voltages are present at this time, all operating
measured values are close to zero. Deviations of the last digit are insignificant. The
measured values are automatically updated.
In the same manner, other measured and counter values can be read out.
0601
IL1
0602
IL2
0603
IL3
0610
3I0 (zero sequence)
0619
3I1 (positive sequence)
0620
3I2 (negative sequence)
®
Figure 3-9
DIGSI
4 — Table of secondary operating measured values – example
The read-out of operating messages is described to serve as an additional example.
Double click on Annunciation in the navigation window.
G
Click on Event Log in the function selection.
G
The present date and time are shown in the data window.
G
Double click on this entry in the data window.
A table of the accumulated event messages is displayed. See Figure 3-10as an ex-
ample. The number designation for an event is provided with a description of the mes-
sage. The corresponding cause, value (ON or OFF), and date and time of the event
are given. The events are listed chronologically; the newest message is shown first.
Initial Inspections
0.00 A
0.00 A
0.00 A
0.00 A
0.00 A
0.00 A
3-9