Functions

6.13.3 Settings

Addr.
Setting Title
3001
Sens. Earth Flt
3002
3U0>
3003
Uph-e min
3004
Uph-e max
3005
3I0>
3006
T Sens.E/F
3007
T 3U0>
3008A
TRIP Direction
3010
CT Err. I1
3011
CT Err. F1
3012
CT Err. I2
3013
CT Err. F2
6-186
F1 (address 3011 ) of the c.t. with its associated current CT Err. I1 (address 3010 )
as well as a further c.t. operating point CT Err. F2 / CT Err. I2 (address 3013 and
3012 ), above which the angle displacement remains practically constant (see Figure
6-100), are set. The relay then approximates, with adequate accuracy, the character-
istic of the transformer. In isolated networks this angle error compensation is not nec-
essary.
∆ϕ
I1
F2
F1
Figure 6-100 Settings for the phase angle correction
Note: The indicated secondary current values refer to current input I
pendent from the nominal value of the device.
Setting Options
Alarm Only
ON
OFF
1..150 V
10..100 V
10..100 V
0.003..1.000 A
0.00..320.00 sec
0.00..320.00 sec
Forward
Reverse
Non-Directional
0.003..1.600 A
0.0..5.0 °
0.003..1.600 A
0.0..5.0 °
Default Setting
Alarm Only
Sensitive Earth Flt.(comp/ isol.
starp.)
50 V
3U0> pickup
40 V
Uph-e min of faulted phase
75 V
Uph-e max of healthy phases
0.050 A
3I0> Release directional ele-
ment
1.00 sec
Time delay for sens. E/F detec-
tion
0.00 sec
Time delay for sens. E/F trip
Forward
Direction for sens. E/F trip
0.050 A
Current I1 for CT Angle Error
0.0 °
CT Angle Error at I1
1.000 A
Current I2 for CT Angle Error
0.0 °
CT Angle Error at I2
I2
I
. They are inde-
4
Comments
7SA6 Manual
C53000-G1176-C156-2