7.1.1.2

Event Log (Operating Messages)

From the
DeviceFront
:
From PC with
®
DIGSI
4
7SA6 Manual
C53000-G1176-C156-2
Operating messages contain information that the device generates during operation
and about the operation. Up to 200 operating messages are stored in chronological
order in the device. New messages are added at the end of the list. If the memory has
been exceeded, then the oldest message is overwritten for each new message.
Exceeding or undershooting of thresholds, that can be changed by the user himself
(see Section 7.1.3.3), is also displayed in the event log.
Faults in the power system are indicated with " Network Fault " and the present fault
number. The fault messages ( Trip Log ) contain details about the history of faults.
This topic is discussed in Sub-section 7.1.1.3.
Earth faults are indicated with „ Earth Fault " and numbered consecutively (only de-
vices provided with the earth fault detection function). Detailed information on earth
faults messages can be found in Subsection 7.1.1.4., Earth Fault Messages .
All predefined operating messages are listed and explained in a table in the Appendix.
In a specific case, of course, only the appropriate messages appear in the display. The
appendix also shows whether the message is only issued as "ON" (to indicate an
event), or as "ON" and "OFF" (to designate the beginning and end of a condition).
With the device ready for operation, first press the
The first menu item ( Annunciation ) is marked.
key to enter the ANNUNCIATION menu (see Figure 7-1).
Press the
Here, select the menu item Event Log (already marked). The EVENT LOG table ap-
pears.
If no messages are present, then the text " list is empty " appears. Otherwise im-
portant events and changes in conditions are listed in chronological order (see Figure
7-3 as an example). Upon entering the menu, the newest (last) message is displayed
at first. The applicable date and time are noted in the display line directly above the
message. If the memory for the operating messages is not full, then the end of the en-
tries is indicated by " END ".
EVENT LOG
---------------------
06/19/99 11:52:05.625
Reset LED
Example of an operating message
Figure 7-3
The
and
keys can be used to move up and down in the event log.
key to return to the MAIN MENU .
Press the
MENU
Click on Annunciation . The options appear in the data window (Figure 7-4).
Double click on the desired message group in the data window, in this case Event
Log . A date and time appear in the data window as shown in Figure 7-4.
Double click on the date and time and the contents of the message group are dis-
played in another window.
MENU
19/19
ON
in the operating field of the device
Control During Operation
key. The MAIN MENU appears.
7-5

Advertisement

Table of Contents
loading