Virtual Outputs - GE Multilin G650 Manual

Generator protection & control system
Hide thumbs Also See for Multilin G650:
Table of Contents

Advertisement

5 SETTINGS
5.6.7.2 VIRTUAL INPUTS STATUS MONITORING:
Actual > Inputs/Outputs > Virtual Inputs > Virtual Input Latched > Virtual Input Self-Reset
Table 5–109: VIRTUAL INPUTS STATUS
VIRTUAL INPUTS LATCHED
LATCHED VIRT IP 1
LATCHED VIRT IP 2
...
LATCHED VIRT IP 32
Text assignment for virtual input is made at Setpoint > Relay Configuration > Virtual Inputs. It should be taken into
account that the text assigned for virtual inputs in the relay configuration screen are only for file management, they are not
sent to the relay.
There are 512 virtual outputs that may be assigned via Logic configuration. If not assigned, the output will be forced to OFF
(Logic 0). An ID may be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of
the logic equations. For more detailed information see chapters 5.8 and 5.9 in this manual.
GEK-113285A
VIRTUAL INPUTS SELF-RESET
SELF-RST VIRT IP 1
SELF-RST VIRT IP 2
...
SELF-RST VIRT IP 32
G650 Generator Protection & Control System
5.6 INPUTS/OUTPUTS

5.6.8 VIRTUAL OUTPUTS

5-121
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents