B.7 MEMORY MAP
ADDRESS BIT
Ajuste Rango de Entrada Analogica J (8 elementos) - Board J Analog Input Range Settings (8 items)
0x31AA
B
...
...
0x31B1
Ajustes Rango de Medida de Entrada Analógica J (8 elementos) - Board J Analog Input Measurement Range Settings (8 items)
0x31B2
0x31B4
...
...
0x31C0
0x31C2
0x31C4
...
...
0x31D0
0x32A4
Ajustes Generales - General Settings
0x218A
0x218C
0x218E
0x2190
0x2192
0x2193
0x2195
0x2196
0x2197
0x2198
0x2199
0x219A
0x2203
B-64
NAME
Range_J_01
...
Range_J_08
Min Value_J_01
Min Value_J_02
...
Min Value_J_08
Max Value_J_01
Max Value_J_02
...
Max Value_J_08
Confirmation address
Phase CT Ratio
Ground CT Ratio
Stv Ground CT Ratio
Phase VT Ratio
Phase VT Connection
Nominal Voltage
Nominal Frequency
Phase Rotation
Frequency Reference
Auxiliary Voltage
Snapshot Events
Freq. Tracking
Confirmation address
G650 Generator Protection & Control System
FORMAT STEP MODE LENGTH MISCELLANEOUS
F012
1
R/W
1
...
...
...
...
F012
1
R/W
1
F003
1
R/W
2
F003
1
R/W
2
...
...
...
...
F003
1
R/W
2
F003
1
R/W
2
F003
1
R/W
2
...
...
...
...
F003
1
R/W
2
W
1
F003
1
R/W
2
F003
1
R/W
2
F003
1
R/W
2
F003
1
R/W
2
F012
1
R/W
1
F003
1
R/W
2
F012
1
R/W
1
F012
1
R/W
1
F012
1
R/W
1
F012
1
R/W
1
F012
1
R/W
1
F012
1
R/W
1
W
1
APPENDIX B
0=NONE
1=-1 to 0 mA
2= 0 to 1mA
3=-1 to 1mA
4= 0 to 5 mA
5= 0 to 10mA
6= 0 to 20mA
7= 4 to 20mA
...
0=NONE
1=-1 to 0 mA
2= 0 to 1mA
3=-1 to 1mA
4= 0 to 5 mA
5= 0 to 10mA
6= 0 to 20mA
7= 4 to 20mA
[-9999.99 , 9999.99]
[-9999.99 , 9999.99]
...
[-9999.99 , 9999.99]
[-9999.99 , 9999.99]
[-9999.99 , 9999.99]
...
[-9999.99 , 9999.99]
[1.0 , 6000.0]
[1.0 , 6000.0]
[1.0 , 6000.0]
[1.0 , 6000.0]
0=WYE
1=DELTA
[1.0 , 500.0] V
0=50 Hz
1=60 Hz
0=ABC
1=ACB
0=VI
1=VII
2=VIII
0=V
X
1=V
N
2=V
G
0=DISABLED
1=ENABLED
0=DISABLED
1=ENABLED
GEK-113285A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents