APPENDIX B
ADDRESS BIT
NAME
Ajustes Derivada de Frecuencia 3-Frequency Rate of Change 3 Settings
0x4170
Function
0x4171
Freq. Rate Trend
0x4172
Freq. Rate Pickup
0x4174
Freq. Rate OV Supv
0x4176
Freq. Rate Min
0x4178
Freq. Rate Max
0x417A
Freq. Rate Delay
0x417C
Snapshot Events
0x418F
Confirmation address
Ajustes Tierra Restringida Grupo 1 - Restricted Gnd Fault 1 Settings(Enhanced models only)
0x4224
Function
0x4225
Ground Fault Pickup
0x4227
Ground Fault Slope
0x4229
Ground Fault Delay
0x422B
Snapshot Events
0x4235
Confirmation address
Ajustes Tierra Restringida Grupo 2 - Restricted Gnd Fault 2 Settings(Enhanced models only)
0x4236
Function
0x4237
Ground Fault Pickup
0x4239
Ground Fault Slope
0x423B
Ground Fault Delay
0x423D
Snapshot Events
0x4247
Confirmation address
Ajustes Tierra Restringida Grupo 3 - Restricted Gnd Fault 3 Settings(Enhanced models only)
0x4248
Function
0x4249
Ground Fault Pickup
0x424B
Ground Fault Slope
0x424D
Ground Fault Delay
0x424F
Snapshot Events
0x4259
Confirmation address
Ajustes Salto Vector Grupo 1 - Loss of Mains 1 Settings(Enhanced models only)
0x425A
Function
0x425B
Loss of Mains Mode
0x425C
Phase Shift Angle
0x425E
Minimum Voltage
0x4260
Snapshot Events
GEK-113285A
FORMAT STEP MODE LENGTH MISCELLANEOUS
F012
1,000 R/W
F012
1,000 R/W
F003
1,000 R/W
F003
1,000 R/W
F003
1,000 R/W
F003
1,000 R/W
F003
1,000 R/W
F012
1,000 R/W
F012
1
F003
1
F003
1
F003
1
F012
1
F012
1
F003
1
F003
1
F003
1
F012
1
F012
1
F003
1
F003
1
F003
1
F012
1
F012
1
F012
1
F003
1
F003
1
F012
1
G650 Generator Protection & Control System
1
0=DISABLED
1=ENABLED
1
0=INCREASING
1=DECREASING
2=BI-DIRECTIONAL
2
[0.10 , 10.00] Hz/s
2
[0.00 , 110.00] %
2
[20.00 , 80.00] Hz
2
[20.00 , 80.00] Hz
2
[0.00 , 60.00] s
1
0=DISABLED
1=ENABLED
W
1
R/W
1
0=DISABLED
1=ENABLED
R/W
2
[0.02 , 20.00] CT
R/W
2
[0.00 , 100.00] %
R/W
2
[0.00 , 600.00] s
R/W
1
0=DISABLED
1=ENABLED
W
1
R/W
1
0=DISABLED
1=ENABLED
R/W
2
[0.02 , 20.00] CT
R/W
2
[0.00 , 100.00] %
R/W
2
[0.00 , 600.00] s
R/W
1
0=DISABLED
1=ENABLED
W
1
R/W
1
0=DISABLED
1=ENABLED
R/W
2
[0.02 , 20.00] CT
R/W
2
[0.00 , 100.00] %
R/W
2
[0.00 , 600.00] s
R/W
1
0=DISABLED
1=ENABLED
W
1
R/W
1
0=DISABLED
1=ENABLED
R/W
1
0=ONE PHASE
R/W
2
[2.00 , 22.00] Deg
R/W
2
[30 , 500] V
R/W
1
0=DISABLED
1=ENABLED
B.7 MEMORY MAP
B
B-127