SPECIFICATIONS
Specifications
NOTE:
NOTE
User interface specifications
Inputs specifications
Outputs specifications
Power supply specifications
1–8
Specifications are subject to change without notice.
GENERAL
LED indicators: .....................................................3 LEDs on the DGT-R (located on the internal transceiver
General device management:...................... Through a PC application
GENERAL
Type: ......................................................................... Dry contact
Coil resistance:.....................................................1400 Ohms maximum
Power draw: .......................................................... 400 mW
GENERAL
Type: ......................................................................... Form-A relay (Service output is Form B)
Contact material:................................................ silver-alloy
Operate time:........................................................ <10 ms
Contact material:................................................ Silver alloy
Continuous carry: ............................................... 5 A
Make and carry for 0.2s:.................................. 30 A per ANSI C37.90
Break (DC inductive, L/R: 40 ms): .................
Voltage
Current
24 V
1 A
48 V
0.5 A
125 V
0.3 A
250 V
0.2 A
POWER SUPPLY
Nominal DC: .......................................................... 125 to 250 V DC
Min/max DC: ......................................................... 100/350 V DC
Nominal AC:........................................................... 120 to 240 V AC at 50/60 Hz
Min/max AC:.......................................................... 88/260 V AC at 50/60 Hz
Voltage loss hold-up: ........................................ >25 ms
Voltage withstand:............................................. 30 V above maximum rating
Power consumption: ......................................... 20 to 30 W typical, 60 W maximum
Internal fusing:.....................................................Ratings: 2 A/600 V
DGT DISTRIBUTED GENERATION TRIP CONTROL SYSTEM – INSTRUCTION MANUAL
module)
6 LEDs on the DGT-D (located on the internal transceiver
module)
11 LEDs on the DGT-U (located on the internal transceiver
module)
Interrupt rating: AC=200,000 A, DC=100,000 A
CHAPTER 1: INTRODUCTION