D.4 IEC 104 SETTINGS
D.4IEC 104 SETTINGS
The Communication settings for IEC 60870-5-104 protocol are the following:
Function:
TCP Port:
Common Addr of ASDU:
D
Cyclic Meter Period:
Synchronization event:
The G650 relay has a custom Binary Inputs points list, called User Map; it is common for any protocol. In the case of IEC
104 Protocol, those points are GROUP1 and GROUP2.
The IEC 104 User Map can be configured using the EnerVista 650 Setup software in Setpoint>Relay Configuration-
>Control Events. The User Map contains 128 Binary Inputs. To each point of the User Map, the user can assign any of the
binary states of the G650 relay, also is possible to combine those states using OR and NOT functions. These states are:
contact inputs and outputs, virtual outputs, protection element states, PLC states, etc. The User Map always has a size of
128 Binary Inputs. Points in the User Map that are not configured will have a zero value in the answer.
It is possible to implement more complex logic than simple OR and NOT using the PLC Editor tool in EnerVista 650 Setup
in the menu Setpoint>Logic Configuration. These complex signals (Virtual Outputs) can be assigned to the binary points
in the Control Events configuration for the IEC 104 user map.
D-4
PRODUCT SETUP>COMMUNICATION SETTINGS >IEC 870-5-104
NAME
Function
TCP Port
Common Addr of ASDU
Cyclic Meter Period
Synchronization Event
G650 Generator Protection & Control System
VALUE
UNITS
DISABLED
2404
255
0
0
Enable or disable the protocol operation.
Listening TCP port in the relay. Default value is 2404.
Address in the ASDU header. Default value is 255.
Number of seconds for instantaneous meterings. 0 means no spontaneous
meterings.
Not implemented.
APPENDIX D
RANGE
[0 : 65535]
[0 : 65535]
[0 : 3600]
[0 : 3600]
GEK-113285A