F.1 FACTORY DEFAULT SETTINGS
SETPOINT > CONTROL ELEMENTS > BREAKER FAILURE(ENHANCED MODELS ONLY)
SETTING DESCRIPTION
Function permission
Supervision (retrip) pickup level
Hiset pickup level
Lowset pickup level
Internal arc pickup level
Internal arc time delay
Retrip time delay
Hiset time delay
Lowset time delay
Second stage time delay
WITHOUT current element time delay No Current Delay
Snapshot event generation
SETPOINT > CONTROL ELEMENTS > VT FUSE FAILURE(ENHANCED MODELS ONLY)
SETTING DESCRIPTION
Function permission
Snapshot event generation
SETPOINT > CONTROL ELEMENTS > FREQUENCY RATE OF CHANGE
FREQUENCY RATE OF CHANGE 1 > FREQUENCY RATE OF CHANGE 2 > FREQUENCY RATE OF CHANGE 3
SETTING DESCRIPTION
Function Permission
F
Direction of the frequency change
Operation Value in Hz/s
Minimum required voltage in %
nominal voltage
Minimum Frequency Threshold
Maximum Frequency Threshold
Frequency rate Trip Delay
Snapshot Events Generation
SETPOINT > CONTROL ELEMENTS > LOSS OF MAINS(ENHANCED MODELS ONLY
LOSS OF MAINS 1 > LOSS OF MAINS 2 > LOSS OF MAINS 3
SETTING DESCRIPTION
Function Permission
Any phase or three phase
displacement mode to operate
Minimum Phase shift angle value to
operate
Minimum voltage threshold
Snapshot Event generation
SETPOINT > CONTROL ELEMENTS > LOSS OF EXCITATION
F-16
NAME
DEFAULT VALUE
Function
DISABLED
Supervision Pickup
1.00
Hiset Pickup
5.00
Lowset Pickup
2.00
Internal Arc Pickup
0.10
Internal Arc Delay
10.00
Supervision Delay
10.00
HiSet Delay
10.00
LowSet Delay
10.00
2nd Step Delay
10.00
10.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
DISABLED
Function
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Freq. Rate Trend
INCREASING
Freq. Rate Pickup
0.50
Freq. Rate OV Supv
40.00
Freq. Rate Min
45.00
Freq. Rate Max
65.00
Freq. Rate Delay
0.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Loss of Mains Mode
ONE PHASE
Phase Shift Angle
1.00
Minimum Voltage
70
Snapshot Events
ENABLED
G650 Generator Protection & Control System
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 A
[0.05 : 160.00]
0.01 A
[0.05 : 160.00]
0.01 A
[0.05 : 160.00]
0.01 A
[0.05 : 160.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
[INCREASING -
N/A
DECREASING - BI-
DIRECTIONAL]
0.01 Hz/s
[0.10 : 10.00]
0.01%
[0.00 : 110.00]
0.01 Hz
[20.00 : 80.00]
0.01 Hz
[20.00 : 80.00]
0.01 s
[0.00 : 60.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[ONE PHASE ]
0.01 Deg
[2.00 : 22.00]
1 V
[30 : 500]
N/A
[DISABLED – ENABLED]
APPENDIX F
USER
VALUE
USER
VALUE
USER
VALUE
USER
VALUE
GEK-113285A