APPENDIX B
ADDRESS BIT
NAME
Ajustes Sobrefrecuencia Grupo 1 - Overfrequency 1 Settings
0x2972
Function
0x2973
Pickup Level
0x2975
Trip Delay
0x2977
Reset Delay
0x2979
Minimum Voltage
0x297B
Snapshot Events
0x298E
Confirmation address
Ajustes Sobrefrecuencia Grupo 2 - Overfrequency 2 Settings
0x298F
Function
0x2990
Pickup Level
0x2992
Trip Delay
0x2994
Reset Delay
0x2996
Minimum Voltage
0x2998
Snapshot Events
0x29AB
Confirmation address
Ajustes Sobrefrecuencia Grupo 3 - Overfrequency 3 Settings
0x29AC
Function
0x29AD
Pickup Level
0x29AF
Trip Delay
0x29B1
Reset Delay
0x29B3
Minimum Voltage
0x29B5
Snapshot Events
0x29C8
Confirmation address
Ajustes Subfrecuencia Grupo 1 - Underfrequency 1 Settings
0x29C9
Function
0x29CA
Pickup Level
0x29CC
Trip Delay
0x29CE
Reset Delay
0x29D0
Minimum Voltage
0x29D2
Snapshot Events
0x29E5
Confirmation address
Ajustes Subfrecuencia Grupo 2 - Underfrequency 2 Settings
0x29E6
Function
0x29E7
Pickup Level
0x29E9
Trip Delay
0x29EB
Reset Delay
0x29ED
Minimum Voltage
0x29EF
Snapshot Events
0x2A02
Confirmation address
GEK-113285A
FORMAT STEP MODE LENGTH MISCELLANEOUS
F012
1
F003
1
F003
1
F003
1
F003
1
F012
1
F012
1
F003
1
F003
1
F003
1
F003
1
F012
1
F012
1
F003
1
F003
1
F003
1
F003
1
F012
1
F012
1
F003
1
F003
1
F003
1
F003
1
F012
1
F012
1
F003
1
F003
1
F003
1
F003
1
F012
1
G650 Generator Protection & Control System
R/W
1
0=DISABLED
1=ENABLED
R/W
2
[20.00 , 65.00] Hz
R/W
2
[0.00 , 900.00] s
R/W
2
[0.00 , 900.00] s
R/W
2
[30 , 500] V
R/W
1
0=DISABLED
1=ENABLED
W
1
R/W
1
0=DISABLED
1=ENABLED
R/W
2
[20.00 , 65.00] Hz
R/W
2
[0.00 , 900.00] s
R/W
2
[0.00 , 900.00] s
R/W
2
[30 , 500] V
R/W
1
0=DISABLED
1=ENABLED
W
1
R/W
1
0=DISABLED
1=ENABLED
R/W
2
[20.00 , 65.00] Hz
R/W
2
[0.00 , 900.00] s
R/W
2
[0.00 , 900.00] s
R/W
2
[30 , 500] V
R/W
1
0=DISABLED
1=ENABLED
W
1
R/W
1
0=DISABLED
1=ENABLED
R/W
2
[20.00 , 65.00] Hz
R/W
2
[0.00 , 900.00] s
R/W
2
[0.00 , 900.00] s
R/W
2
[30 , 500] V
R/W
1
0=DISABLED
1=ENABLED
W
1
R/W
1
0=DISABLED
1=ENABLED
R/W
2
[20.00 , 65.00] Hz
R/W
2
[0.00 , 900.00] s
R/W
2
[0.00 , 900.00] s
R/W
2
[30 , 500] V
R/W
1
0=DISABLED
1=ENABLED
W
1
B.7 MEMORY MAP