GE Multilin G650 Manual page 621

Generator protection & control system
Hide thumbs Also See for Multilin G650:
Table of Contents

Advertisement

F.1 FACTORY DEFAULT SETTINGS
SETPOINT > PROTECTION ELEMENTS > POWER > DIRECTIONAL POWER>
DIRECTIONAL POWER 1> DIRECTIONAL POWER 2 > DIRECTIONAL POWER 3
SETTING DESCRIPTION
Function permission
Block from off-line
Directional Angle for stage 1
Pickup level for stage 1
Trip time for stage 1
Directional Angle for stage 2
Pickup level for stage 2
Trip time for stage 2
Snapshot Event generation
SETPOINT > PROTECTION ELEMENTS > POWER > POWER FACTOR LIMITING(ENHANCED MODELS ONLY)>
PWR FACTOR LIMITING 1> PWR FACTOR LIMITING 2 > PWR FACTOR LIMITING 3
SETTING DESCRIPTION
Function permission
Pickup level for PF Lead Stage1
Pickup level for PF Lag Stage1
Trip time for PF Stage1
Pickup level for PF Lead Stage2
Pickup level for PF Lag Stage2
Trip time for PF Stage2
Snapshot Event generation
SETPOINT > CONTROL ELEMENTS > SETTING GROUP
F
SETTING DESCRIPTION
Setting Grouping Permission
Active Group
Snapshot Event generation
SETPOINT > CONTROL ELEMENTS > UNDERFREQUENCY
UNDERFREQUENCY 1 > UNDERFREQUENCY 2 > UNDERFREQUENCY 3
SETTING DESCRIPTION
Function permission
Pickup level
Trip time
Reset time
Minimum voltage threshold
Snapshot event generation
F-14
NAME
DEFAULT VALUE
Function
DISABLED
Blk Time After Close
0.00
Dir Power Angle 1
0.00
Stage 1 Tap
10.00
Stage 1 Time
60.00
Dir Power Angle 2
0.00
Stage 2 Tap
20.00
Stage 2 Time
60.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
PF Lead Stg1 Level
0.99
PF Lag Stg1 Level
0.80
PF Stg1 Trip Delay
1.0
PF Lead Stg2 Level
0.99
PF Lag Stg2 Level
0.75
PF Stg2 Trip Delay
1.0
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Active Group
GROUP 1
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
49.50
Trip Delay
0.00
Reset Delay
0.00
Minimum Voltage
0
Snapshot Events
ENABLED
G650 Generator Protection & Control System
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 s
[0.00 : 900.00]
0.01 Deg
[0.00 : 359.99]
0.01MW
[-10000.00 : 10000.00]
0.01 s
[0.00 : 900.00]
1 Deg
[0.00 : 359.99]
0.01MW
[-10000.00 : 10000.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01
[0.05 : 0.99]
0.01
[0.05 : 0.99]
0.1 s
[0.2 : 300.0]
0.01
[0.05 : 0.99]
0.01
[0.05 : 0.99]
0.1 s
[0.2 : 300.0]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
[GROUP 1 – GROUP 2 –
N/A
GROUP 3]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 Hz
[20.00 : 65.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
1 V
[30 : 00]
N/A
[DISABLED – ENABLED]
APPENDIX F
USER
VALUE
USER
VALUE
USER
VALUE
USER
VALUE
GEK-113285A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents