GE Multilin G650 Manual page 184

Generator protection & control system
Hide thumbs Also See for Multilin G650:
Table of Contents

Advertisement

5 SETTINGS
Table 5–39: PHASE TIME OVERCURRENT SETTINGS
SETPOINT > PROTECTION ELEMENTS > PHASE CURRENT >
> PHASE TOC HIGH > PHASE TOC HIGH 1> PHASE TOC HIGH 2 > PHASE TOC HIGH 3
> PHASE TOC LOW > PHASE TOC LOW 1 > PHASE TOC LOW 2 > PHASE TOC LOW 3
SETTING DESCRIPTION
Function permission
Input type
Pickup level
Curve shape
Time Dial
Reset type
Voltage Restraint
Snapshot Event generation
If the voltage restraint feature is disabled, the pickup level always remains at the value set in the Pickup Level setting.
The snapshot event setting enables or disables the snapshot event generation for the phase time overcurrent elements.
GEK-113285A
NAME
DEFAULT VALUE
Function
DISABLED
Input
PHASOR(DFT)
Pickup Level
1.00
Curve
IEEE Ext Inv
TD Multiplier
1.00
Reset
INSTANTANEOUS
Voltage Restraint
DISABLED
Snapshot Events
ENABLED
G650 Generator Protection & Control System
5.4 PROTECTION ELEMENTS
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[PHASOR – RMS]
0.01 A
[0.05 : 160.00]
N/A
[See list of curves]
0.01 s
[0.00 : 900.00]
N/A
[INSTANTANEOUS – LINEAR]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
5
5-41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents