Optic Features - GE Multilin G650 Manual

Generator protection & control system
Hide thumbs Also See for Multilin G650:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
Wave length: 1300nm
Connector types: ST package style
Fiber type: multimode 62.5/125 μm or 50/125 μm
TRANSMITTER CHARACTERISTICS
Parameter
Output Optical Power
62.5/125 μm, NA = 0.275 Fiber
Output Optical Power
50/125 μm, NA = 0.275 Fiber
Output Optical Power at
Logic "0" State
RECEIVER CHARACTERISTICS
Parameter
Input Optical Power
Minimum at Window Edge
Input Optical Power
Minimum at Eye Center
Input Optical Power Maximum
Notes:
1.
These optical power values are measured with the following conditions:
The Beginning of Live (BOL) to the End of Life (EOL) optical power degradation is typically 1.5 dB per industry
convention for long wavelength LEDs. The actual degradation observed in Agilent's 1300nm LED products is <1 dB, as
specified in this data sheet.
Over the specified operating voltage and temperature ranges.
With HALT Line State, (12.5 MHz square-wave), input signal.
At the end of one meter of noted optical fiber with cladding modes removed.
The average power value can be converted to a peak power value by adding 3 dB. Higher output optical power
transmitters are available on special request.
2.
The transmitter provides compliance with the need for Transmit_Disable commands from the FDDI SMT layer by
providing an Output Optical Power level of <-45 dBm average in response to a logic "0" input. This specification applies
to either 62.5/125 μm or 50/125 μm fiber cables.
3.
This specification is intended to indicate the performance of the receiver section of the transceiver when Input Optical
Power signal characteristics are present per the following definitions. The Input Optical Power dynamic range from the
minimum level (with a window time-width) to the maximum level is the range over which the receiver is guaranteed to
provide output data with a Bit Error Ratio (BER) better than or equal to 2.5e-10.
At the Beginning of Life (BOL).
Over the specified operating temperature and voltage ranges.
4.
All conditions for Note 3 apply except that the measurement is made at the center of the symbol with no window time-
width.
GEK-113285A
Min.
BOL
-19
EOL
-20
BOL
-22.5
EOL
-23.5
Min.
-14
G650 Generator Protection & Control System
2.4 TECHNICAL SPECIFICATIONS
Typ.
Max.
Unit
Reference
-14
dBm avg.
Note 1
-14
dBm avg.
Note 1
-45
dBm avg.
Note 2
Typ.
Max.
Unit
Reference
-33.9
-31
dBm avg.
Note 3
-35.2
-31.8
dBm avg.
Note 4
dBm avg.
Note 3

2.4.11 OPTIC FEATURES

2-31
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents