C.4 BINARY INPUT POINTS
C.4BINARY INPUT POINTS
The G650 relay has a configurable Map of DNP Binary Input points. This map can be formed by up to 10 blocks of 16
binary states that are configured using "Setpoint->Relay Configuration" menu from the EnerVista 650 Setup program. The
minimum number of DNP Binary Input points is 16 and the maximum number is 160. Within these 160 DNP points, 128 bits
(8 blocks of 16) are mapped to Control Events ("Setpoint->Relay Configuration->Control Events") and 32 bits (2 block
of 16) are mapped to contacts A, B of 16 Switchgears ("Setpoint->Relay Configuration->Switchgear"). Each Switchgear
in G650 is mapped into two DNP Binary Input points. Lets say the setting Binary Input Block1 has been set the value
Switchgear 1-8, it means that DNP Binary Input point 0 = Switchgear 1Contact A, DNP Binary Input point 1 = Switchgear 1
Contact B, DNP Binary Input point 2 = Switchgear 2 Contact A, etc.
To each Control Event or Switchgear Contact, the user can assign any of the binary states of the G650 relay. These states
are contact inputs and outputs, virtual outputs, protection element states, PLC states, etc. DNP Points that correspond to
Control Events o Switchgear Contacts that are not configured will have a zero value in the response.
Using the PLC-Editor, through the EnerVista 650 Setup program, selecting menu: "Setpoint->Logic Configuration", it will
C
be possible to implement complex logic, more than simple OR and NOT previous functions. To perform this, in the menu:
"Setpoint->Relay Configuration->Control Events" assign a Virtual Output to selected point, after that, implement wished
logic with the PLC-Editor.
BINARY INPUT POINTS
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read), 22 (assign class)
Static Variation Reported when variation 0 requested: 2 (Binary Input Change with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Default Class for all points: 1
DEFAULT BINARY INPUT POINTS MAP
POINT
INDEX
0-127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
C-10
NAME/DESCRIPTION
Control Events 1-128
Switchgear 1 Contact A
Switchgear 1 Contact B
Switchgear 2 Contact A
Switchgear 2 Contact B
Switchgear 3 Contact A
Switchgear 3 Contact B
Switchgear 4 Contact A
Switchgear 4 Contact B
Switchgear 5 Contact A
Switchgear 5 Contact B
Switchgear 6 Contact A
Switchgear 6 Contact B
Switchgear 7 Contact A
Switchgear 7 Contact B
Switchgear 8 Contact A
G650 Generator Protection & Control System
143
Switchgear 8 Contact B
144
Switchgear 9 Contact A
145
Switchgear 9 Contact B
146
Switchgear 10 Contact A
147
Switchgear 10 Contact B
148
Switchgear 11 Contact A
149
Switchgear 11 Contact B
150
Switchgear 12 Contact A
151
Switchgear 12 Contact B
152
Switchgear 13 Contact A
153
Switchgear 13 Contact B
154
Switchgear 14 Contact A
155
Switchgear 14 Contact B
156
Switchgear 15 Contact A
157
Switchgear 15 Contact B
158
Switchgear 16 Contact A
159
Switchgear 16 Contact B
APPENDIX C
GEK-113285A