GE Multilin G650 Manual page 510

Generator protection & control system
Hide thumbs Also See for Multilin G650:
Table of Contents

Advertisement

APPENDIX B
ADDRESS BIT
NAME
Ajustes Subtensión Auxiliar Grupo 1 - Auxiliary UV 1 Settings
0x282E
Function
0x282F
Pickup Level
0x2831
Curve
0x2832
Delay
0x2834
Snapshot Events
0x2847
Confirmation address
Ajustes Subtensión Auxiliar Grupo 2 - Auxiliary UV 2 Settings
0x2848
Function
0x2849
Pickup Level
0x284B
Curve
0x284C
Delay
0x284E
Snapshot Events
0x2861
Confirmation address
Ajustes Subtensión Auxiliar Grupo 3 - Auxiliary UV 3 Settings
0x2862
Function
0x2863
Pickup Level
0x2865
Curve
0x2866
Delay
0x2868
Snapshot Events
0x287B
Confirmation address
Ajustes Sobretensión de Fases Grupo 1 - Phase OV 1 Settings
0x287C
Function
0x287D
Pickup Level
0x287F
Trip Delay
0x2881
Reset Delay
0x2883
Logic
0x2884
Snapshot Events
0x2897
Confirmation address
GEK-113285A
FORMAT STEP MODE LENGTH MISCELLANEOUS
F012
1
F003
1
F012
1
F003
1
F012
1
F012
1
F003
1
F012
1
F003
1
F012
1
F012
1
F003
1
F012
1
F003
1
F012
1
F012
1
F003
1
F003
1
F003
1
F012
1
F012
1
G650 Generator Protection & Control System
R/W
1
0=DISABLED
1=ENABLED
R/W
2
[3 , 500] V
R/W
1
0=DEFINITE TIME
1=INVERSE TIME
R/W
2
[0.00 , 900.00] s
R/W
1
0=DISABLED
1=ENABLED
W
1
R/W
1
0=DISABLED
1=ENABLED
R/W
2
[3 , 500] V
R/W
1
0=DEFINITE TIME
1=INVERSE TIME
R/W
2
[0.00 , 900.00] s
R/W
1
0=DISABLED
1=ENABLED
W
1
R/W
1
0=DISABLED
1=ENABLED
R/W
2
[3 , 500] V
R/W
1
0=DEFINITE TIME
1=INVERSE TIME
R/W
2
[0.00 , 900.00] s
R/W
1
0=DISABLED
1=ENABLED
W
1
R/W
1
0=DISABLED
1=ENABLED
R/W
2
[3 , 500] V
R/W
2
[0.00 , 900.00] s
R/W
2
[0.00 , 900.00] s
R/W
1
0=ANY PHASE
1=TWO PHASES
2=ALL PHASES
R/W
1
0=DISABLED
1=ENABLED
W
1
B.7 MEMORY MAP