Event Structure; B.5.2 Event Structure - GE Multilin G650 Manual

Generator protection & control system
Hide thumbs Also See for Multilin G650:
Table of Contents

Advertisement

APPENDIX B
Each event has 14 bytes, being its format:
- Short (2 bytes):
- Short (2 bytes):
- Short (2 bytes):
- Double unsigned (8 bytes):
The 0xFCFF-address usefulness is for when it is desired to read all the available events in the G650, something that will be
done following a master start up.
WARNING! Unlike a standard ModBus address, these addresses consist of 14 bytes each one, instead of the 2 used in
ModBus. This way, each event, which has a structure of 14 bytes, will be contained in one address, as shown on the table
below:
0xFD00
1byte
1byte
1byte
............
0xFDFF 1byte
1byte
1byte
Imagine that the events buffer contains the following information:
Event
7424
7425
Number
Address
0xFD00
0xFD01
105 registers: 15 events * 7 registers.
(NOTE: the 0x03FF address will have the event number 7677 because the 7676 is the last one).
a) EVENTS COLLECTION PROCESS
ALL EVENTS
There are two possibilities:
First possibility: start in 0xFCFF address and read events 15 by 15. The frame sent to the relay is the following one:
GEK-113285A
event number (0 - 2^12 + carry bit)
events bit number (from 0 to 191).
the 0 bit indicates the event value (0 or 1) and the 15 bit whether it is event (to
distinguish not valid values, in case of everything was set to 0)
milliseconds from 1 January 2000
1byte
1byte
1byte
1byte
1byte
1byte
1byte
1byte
..........
7675
0xFDFB
G650 Generator Protection & Control System

B.5.2 EVENT STRUCTURE

1byte
1byte
1byte
1byte
1byte
1byte
1byte
1byte
7676
7421
0xFDFC
0xFDFD
B.5 OUTPUT WRITING
1byte
1byte
1byte
1byte
1byte
1byte
7422
7423
0xFDFE
0xFDFF
B-15