Outputs - GE Multilin G650 Manual

Generator protection & control system
Hide thumbs Also See for Multilin G650:
Table of Contents

Advertisement

5.6 INPUTS/OUTPUTS
5.6.4.1 OUTPUT SETTINGS DESCRIPTION
Output Logic_0X _0Z: Type of logic applied to outputs. Possible values are positive and negative. The default value is
positive. Depending on the type of setting selected, the physical output will be in the same direction (positive) or opposite
(negative) the output activation command.
Output Type_0X _0Z: Type of output adjusted. Possible values are normal, pulse or latched, the default value is Normal.
Normal:
Pulse:
according to the Pulse Output Time setting.
Latched:
outputs is configured at Setpoint > Relay Configuration > Outputs > Contact Output Reset".
Pulse Output Time_0X _0Z: This is the length of the output pulse in case the output type is selected as pulse; the default
value is 10000 ms.
Figure 5–28:shows the types of signals associated to the different output configuration types
5
5-108
The contact output follows the activation command. Remains active while the operation signal is active.
The contact output remains active the time the operation signal is active plus the pulse output time,
The output remains active after the operation signal has been cleared. The reset signal for the latched
Figure 5–28: OUTPUT LOGIC TYPES.
G650 Generator Protection & Control System
5 SETTINGS

5.6.4 OUTPUTS

.
GEK-113285A