5.4 PROTECTION ELEMENTS
5.4.2.5
I2T CURVES
The following formulas define this type of curves:
where:
t = Operation time in seconds
Dial = multiplier setting
I = Input current
Itap = Current pickup value
T
= reset time in seconds
RESET
Table 5–37: TRIPPING TIME IN SECONDS FOR I2T CURVES
DIAL
CURRENT (I/ITAP)
1.5
5
0.01
0.444
0.10
4.444
1.00
44.444
10.00
444.444
100.00
4444.444
600.00
26666.667 15000.000 6666.667
5.4.2.6 DEFINITE TIME CURVES
The definite time makes the element trip when the current value is maintained beyond the pickup value during a longer time
period than the set value. The Dial setting allows modifying this time frame from instantaneous to 900 seconds in steps of
10 ms.
5.4.2.7 RECTIFIER TIME CURVES
Rectifier curves are generated from the following formulas:
where:
T = Operation time (in seconds).
TDM = Multiplying factor
I = Input current
I
= Pickup current
pickup
T
= Reset time (in seconds) assuming a 100% of power capacity and that the reset is activated
reset
5-38
2.0
3.0
4.0
0.250
0.111
0.063
2.500
1.111
0.625
25.000
11.111
6.250
250.000
111.111
62.500
2500.000
1111.111
625.000
3750.000
G650 Generator Protection & Control System
5.0
6.0
7.0
0.040
0.028
0.020
0.400
0.278
0.204
4.000
2.778
2.041
40.000
27.778
20.408
400.000
277.778
204.082
2400.000
1666.667
1224.490
5 SETTINGS
8.0
9.0
10.0
0.016
0.012
0.010
0.156
0.123
0.100
1.563
1.235
1.000
15.625
12.346
10.000
156.250
123.457
100.000
937.500
740.741
600.000
GEK-113285A