8 BOOTCODE AND FIRMWARE UPGRADE

8.3 FIRMWARE VERSION UPGRADE

8.3FIRMWARE VERSION UPGRADE
The relay settings and configuration will be lost, so it is advisable to save them to a file. Take into account that if the
boot code has been previously upgraded, all the data (including calibration settings) was lost.
In case of error during the firmware upgrading process, the user could repeat the whole process as many times as
necessary, this is possible thanks to an independent boot memory (bootcode).
The firmware upgrading process should be done using the EnerVista 650 Setup software, after connecting the relay by
Ethernet port (COM3).

8.3.1 FIRMWARE UPGRADE

1
Once the communication with the relay through Ethernet connection has been verified
, enter the EnerVista 650 Setup
program, select Communication and the Upgrade Firmware Version option.
Therefore, it is necessary to save all settings to a file before following with the process.
Figure 8–16: FIRMWARE-BOOT VERSION COMPATIBILITY
After accepting to proceed, a window will open up for the upgrade parameter.t is also necessary to enter the ordering code
for the relay. See figure below:
8
1. Calibration settings should be stored in a file before upgrading the firmware.
Go to EnerVista 650 Setup main menu "Communication > Calibration > Get Calibration Settings"
Store the file in the PC using the relay serial number, for instance, as the name of the file.
GEK-113285A
G650 Generator Protection & Control System
8-9