2.4 TECHNICAL SPECIFICATIONS
Level Accuracy
Timing accuracy
Snapshot Events
2.4.2.4 PULSE COUNTERS
2
Number of Pulse counters available
Multiplier factor
Overload factor
Board Origin
Input origin
2.4.2.5 ANALOG COMPARATORS
Analog Input
Analog Maximum Threshold value
Analog Minimum Threshold value
Analog Delay
Analog Hysteresis
Analog Direction (for activation inside or outside the
deadband)
2-18
±0.5% of the reading ± 10 mA from 0.05 to 10 A
±1.5% of the reading for higher values.
±3.5% of operate time or 50 ms. (whichever is greater)
Selectable by setting
G650 Generator Protection & Control System
2 PRODUCT DESCRIPTION
Up to 8
0.000 to 65000.000 in steps of 0.001
0 to 1000000 in steps of 1
All available input/outputs boards in the device. See
ordering code [F, G, H, J]
up to 32 [depending on the board type selection]
Any analog value available in the device
-100000.000 to 100000.000 in steps of 0.001
-100000.000 to 100000.000 in steps of 0.001
0.00 to 900.00 in steps of 0.01
0.0 to 50.00 in steps of 0.1
IN or OUT
GEK-113285A