4.2 HUMAN MACHINE INTERFACE (HMI)
<ACK ALL>
This option acknowledges all alarms. Alarm acknowledgement through the graphic HMI is considered as through
communication port COM2, as it is considered to be Local in both cases.
When an alarm has been acknowledged, a selection mark will appear to the right of its status. Inactive alarms will
disappear from the screen once they are acknowledged.
4.2.6.6 INPUT/OUTPUT MONITORING SCREEN
This is the last screen available in the graphic display. This screen allows viewing the status of the relay inputs and outputs,
as well as emulate inputs (for verification of the logic, or related functions), and contact outputs (to verify wiring).
The format of this screen is shown on the figure below.
4
The first line shows the name of the screen "I/O Cards", followed by the type and description of the board where the cursor
is located, which will appear between selection marks > < and blinking.
The navigation legend on this screen is as follows:
Esc: Prev.
This option returns to the previous screen (Alarms Panel).
Intro: Menu.
This option provides access to the selected I/O board menu:
This menu includes the following options.
next
view
As in previous screens, to access the different options provided by the inputs/outputs graphic menu, the user must move
the shuttle key left to right. The selected option will be displayed in upper case and between brackets. To access the
selected option, the shuttle key must be pressed.
4-58
Type: 2,
>F<
G
H
J
Esc: Prev.
Intro: Menu.
Figure 4–31: INPUTS/OUTPUTS GENERAL SCREEN
Esc: Prev.
test input
test output
G650 Generator Protection & Control System
4 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES
IO Card.
Nº IN 8,
Nº OUT 8
L-R: Chg Card.
Intro: Menu.
L-R: Chg Card
GEK-113285A