GE Multilin G650 Manual page 148

Generator protection & control system
Hide thumbs Also See for Multilin G650:
Table of Contents

Advertisement

5 SETTINGS
PRODUCT SETUP>COMMUNICATION SETTINGS >DNP3 SLAVE
DNP3 SLAVE 1 > DNP3 SLAVE 2 > DNP3 SLAVE 3
Binary Input Block 6
Binary Input Block 7
Binary Input Block 8
Binary Input Block 9
Binary Input Block 10
5.2.1.5 IEC 60870-5-104
Communication settings for IEC 60870-5-104 protocol. For more detailed information go to appendix D in this manual.
Table 5–6: IEC 60870-5-104 PROTOCOL SETTINGS
PRODUCT SETUP > COMMUNICATION SETTINGS >IEC 870-5-104
Name
Function
TCP Port
Common Addr of ASDU
Cyclic Meter Period
Synchronization Event
5.2.1.6 SNTP
Table 5–7: SNTP PROTOCOL SETTINGS
PRODUCT SETUP > COMMUNICATION SETTINGS >SNTP
Name
Function
UDP Port
Server Ip Oct1
Server Ip Oct2
Server Ip Oct3
Server Ip Oct4
The G650 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the G650 can obtain the clock
time over an Ethernet network. The G650 acts as an SNTP client to receive time values from an SNTP/NTP server, usually
a dedicated product using a GPS receiver to provide an accurate time. Three different modes of SNTP operation are
supported. These modes are unicast, broadcast and anycast.
If SNTP functionality is enabled at the same time as an IRIG-B source is connected to the G650, the IRIG-B signal provides
the time value to the G650 clock for as long as a valid signal is present. If the IRIG-B signal is removed, the time obtained
from the SNTP server is used.
To use SNTP in unicast mode, Server IP Oct1...4 must be set to the SNTP/NTP server IP address. Once this address is
set and the Function setting is "UNICAST", the G650 attempts to obtain time values from the SNTP/NTP server. Since
many time values are obtained and averaged, it generally takes forty seconds until the G650 clock is synchronized with the
SNTP/NTP server. It may take up to one minute for the G650 to signal an SNTP FAIL state if the server is off-line.
To use SNTP in broadcast mode, set the Function setting to "BROADCAST". The G650 then listens to SNTP messages
sent to the "all ones" broadcast address for the subnet. The G650 waits up to eighteen minutes (>1024 seconds) without
receiving an SNTP broadcast message before signalling an SNTP FAIL state.
GEK-113285A
CTL EVENTS 81-96
CTL EVENTS 97-112
CTL EVENTS 113-128
SWITCHGEAR 1-8
SWITCHGEAR 9-16
Default Value
DISABLED
2404
255
0
0
Default Value
DISABLED
123
0
0
0
0
G650 Generator Protection & Control System
N/A
N/A
N/A
N/A
N/A
Step
Range
N/A
[DISABLED-UNICAST–
BROADCAST- ANYCAST]
1
[1 : 65535]
1
[0 : 65535]
1
[0 : 3600]
1
[0 : 3600]
Step
Range
N/A
[DISABLED – ENABLED]
1
[1 : 65535]
1
[0 : 255]
1
[0 : 255]
1
[0 : 255]
1
[0 : 255]